Yaskawa Z1000 AC Drive HVAC User Manual

Page 279

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

F7-09

(3ED)

<6>

Gateway Address 1

Gateway IP Add 1

Sets the most significant octet of network Gateway address.

Default: 192

Min.: 0

Max.: 255

F7-10

(3EE)

<6>

Gateway Address 2

Gateway IP Add 2

Sets the second most significant octet of network Gateway

address.

Default: 168

Min.: 0

Max.: 255

F7-11

(3EF)

<6>

Gateway Address 3

Gateway IP Add 3

Sets the third most significant octet of network Gateway

address.

Default: 1

Min.: 0

Max.: 255

F7-12

(3E0)

<6>

Gateway Address 4

Gateway IP Add 4

Sets the fourth most significant octet of network Gateway

address.

Default: 1

Min.: 0

Max.: 255

F7-13

(3F1)

Address Mode at Startup

IP Add Mode Sel

0: User Defined

1: BOOTP

2: DHCP

Select the option address setting method
0: Static

<5> <6>

1: BOOTP

2: DHCP

Default: 2

Range: 0 to 2

F7-14

(3F2)

Duplex Mode Selection

Duplex Select

0: Half Duplex

1: Auto Negotiate

2: Full Duplex

Selects duplex mode setting.
0: Half duplex forced

<7>

1: Auto-negotiate duplex mode and communication speed
2: Full duplex forced

<7>

Default: 1

Range: 0 to 2

F7-15

(3F3)

<7>

Communication Speed

Selection

Baud Rate

10: 10 Mbps

100: 100 Mbps

Sets the communication speed

10: 10 Mbps

100: 100 Mbps

Default: 10

Range: 10, 100

F7-16

(3F4)

Communication Loss

Timeout

CommLoss Tout

Sets the timeout value in 0.1 s for communication loss

detection.

Example: Setting this parameter to 100 represents 10.0 seconds.

Setting this parameter to 0 disables the connection timeout.

Default: 0

Min.: 0

Max.: 300

F7-17

(3F5)

EtherNet/IP Speed

Scaling Factor

EN Speed Scale

Sets the scaling factor for the speed monitor in EtherNet/IP

Class ID 2AH Object.

Default: 0

Min.: -15

Max.: 15

F7-18

(3F6)

EtherNet/IP Current

Scaling Factor

EN Current Scale

Sets the scaling factor for the output current monitor in

EtherNet/IP Class ID 2AH Object.

Default: 0

Min.: -15

Max.: 15

F7-19

(3F7)

EtherNet/IP Torque

Scaling Factor

EN Torque Scale

Sets the scaling factor for the torque monitor in EtherNet/IP

Class ID 2AH Object.

Default: 0

Min.: -15

Max.: 15

F7-20

(3F8)

EtherNet/IP Power

Scaling Factor

EN Power Scale

Sets the scaling factor for the power monitor in EtherNet/IP

Class ID 2AH Object.

Default: 0

Min.: -15

Max.: 15

F7-21

(3F9)

EtherNet/IP Voltage

Scaling Factor

EN Voltage Scale

Sets the scaling factor for the voltage monitor in EtherNet/IP

Class ID 2AH Object.

Default: 0

Min.: -15

Max.: 15

F7-22

(3FA)

EtherNet/IP Time

Scaling

EN Time Scale

Sets the scaling factor for the time monitor in EtherNet/IP Class

ID 2AH Object.

Default: 0

Min.: -15

Max.: 15

F7-23 to

F7-32

(3FB to

374)

Dynamic Output

Assembly Parameters

Parameters used in Output Assembly 116.

Each parameter contains a MEMOBUS/Modbus address. The

value received for Output Assembly 116 will be written to the

corresponding MEMOBUS/Modbus address.

A MEMOBUS/Modbus address value of 0 means the value

received for Output Assembly 116 will not be written to any

register.

Default: 0

F7-33 to

F7-42

(375 to

37E)

Dynamic Input

Assembly Parameters

Parameters used in Input Assembly 166.

Each parameter contains a MEMOBUS/Modbus address. The

value sent for Input Assembly 166 will be read from the

corresponding MEMOBUS/Modbus address.

A MEMOBUS/Modbus address value of 0 means the value sent

for Input Assembly 166 is not defined, and the default register

value will be returned.

Default: 0

<1> When using this setting, be sure to take safety measures, such as installing an emergency stop switch. The drive will continue to operate when a

fault is detected.

<3> Parameter setting value is not reset to the default value when the drive is initialized.
<4> Cycle power for setting changes to take effect.

B.6 F: Communication Option Parameters

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual

279

B

Parameter List