Setting 0: MEMOBUS/Modbus
Setting 1: N2 (Metasys)
Setting 2: P1 (APOGEE FLN)
Setting 3: BACnet

n

H5-09: Communications Fault Detection Time

Sets the time the communications must be lost before the drive triggers a CE fault.

No.

Name

Setting Range

Default

H5-09

Communications Fault Detection Time

0.0 to 10.0 s

2.0 s

n

H5-10: Unit Selection for MEMOBUS/Modbus Register 0025H

Sets the unit for the output voltage monitor value in MEMOBUS/Modbus register 0025H.

No.

Name

Setting Range

Default

H5-10

Unit Selection for MEMOBUS/Modbus Register 0025H

0 or 1

0

Setting 0: 0.1 V units
Setting 1: 1 V units

n

H5-11: Communications Enter Function Selection

Selects whether an Enter command is necessary to change parameter values via MEMOBUS/Modbus communications.

Refer

to Enter Command on page 333

.

No.

Name

Setting Range

Default

H5-11

Communications Enter Function Selection

0 or 1

0

Setting 0: Enter command necessary

Parameter changes become effective after an Enter command. An Enter command must only be sent after the last parameter

change, not for each single parameter.

Setting 1: Enter command not necessary

Parameter value changes become effective immediately without the need to send an Enter command.

n

H5-12: Run Command Method Selection

Selects the type of sequence used when the Run command source is set to MEMOBUS/Modbus communications

(b1-02, b1-16 = 2).

No.

Name

Setting Range

Default

H5-12

Run Command Method Selection

0 or 1

0

Setting 0: FWD/Stop, REV/Stop

Setting bit 0 of MEMOBUS/Modbus register 0001H will start and stop the drive in the forward direction. Setting bit 1 will

start and stop the drive in reverse.

Setting 1: Run/Stop, FWD/REV

Setting bit 0 of MEMOBUS/Modbus register 0001H will start and stop the drive. Setting bit 1 changes the direction.

n

L5-02: Auto Restart Fault Output Operation Selection

Determines if a fault output is triggered (H2- = E) when the drive attempts to restart.

No.

Name

Setting Range

Default

L5-02

Auto Restart Fault Output Operation Selection

0, 1

0

Setting 0: No Fault Output
Setting 1: Fault Output Is Set

n

L5-04: Fault Reset Interval Time

Determines the amount of time to wait between restart attempts when parameter L5-05 is set to 1.

4.13 Advanced Drive Setup Adjustments

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual

173

4

Start-Up Programming & Operation