4.11 Verifying Parameter Settings and Backing Up Changes

Use the Verify Menu to check all changes to parameter settings.

Refer to Verifying Parameter Changes: Verify Menu on

page 110

.

Save the verified parameter settings. Change the access level or set a password to the drive to prevent accidental modification

of parameter settings.

u

Backing Up Parameter Values: o2-03

Setting o2-03 to 1 saves all parameter settings before resetting o2-03 to 0. The drive can now recall all the saved parameters

by performing a User Initialization (A1-03 = 1110).

No.

Parameter

Name

Description

Setting

Range

Default

Setting

o2-03

User Parameter

Default Values

Lets the user create a set of default settings for a User Initialization.

0: Saved/Not Set

1: Set Defaults - Saves current parameter settings as the default values for a User

Initialization.

2: Clear All - Clears the currently saved user settings. After saving the user parameter set

value, the items of 1110 (User Initialization) are displayed in A1-03 (User Parameter Default

Value).

0 to 2

0

A1-03

Initialize

Parameters

Selects a method to initialize the parameters.

0: No Initialize

1110: User Initialization (The user must first program and store desired settings using

parameter o2-03)

2220: 2-Wire Initialization (parameter initialized prior to shipment)

3330: 3-Wire Initialization

3410: HVAC Initialization

3420: OEM Bypass Initialization

0 to 3420

0

u

Parameter Access Level: A1-01

Setting the Access Level for “Operation only” (A1-01 = 0) allows the user to access parameters A1- and U- only.

Other parameters are not displayed.
Setting the Access Level for “User Parameters” (A1-01 = 1) allows the user to access only the parameters that have been

previously saved as User Parameters. This is helpful when displaying only the relevant parameters for a specific application.

No.

Parameter

Name

Description

Setting

Range

Default

A1-01

Access Level

Selection

Selects which parameters are accessible via the HOA keypad.

0: Operation only. A1-01 and A1-04 can be set and monitored, and U-parameters can also

be viewed.

1: User Parameters. Only recently changed parameters from application parameters A2-01 to

A2-16 and A2-17 to A2 -32 can be set and monitored.

2: Advanced Access Level. All parameters can be set and monitored.

0 to 2

2

A2-01

to

A2-32

User

Parameters 1

to 32

Parameters selected by the user are saved as User Parameters, including recently viewed

parameters and parameters specifically selected for quick access.

If parameter A2-33 is set to 1, recently viewed parameters will be listed between A2-17 and A2-32.

Parameters A2-01 through A2-16 must be manually selected by the user.

If A2-33 is set to 0, recently viewed parameters will not be saved to the group of User Parameters.

A2- parameters are now available for manual programming.

b1-01 to

o-

A2-33

User

Parameter

Automatic

Selection

0: Parameters A2-01 through A2-32 are reserved for the user to create a group of User Parameters.

1: Save history of recently viewed parameters. Recently edited parameters will be saved to A2-17

through A2-32 for quick access. The most recently changed parameter is saved to A2-17. The

second most recently changed parameter is saved to A2-18, etc.

0, 1

1

u

Password Settings: A1-04, A1-05

The user can set a password in parameter A1-05 to restrict access to the drive. The password must be entered to A1-04 to

unlock parameter access (i.e., parameter setting A1-04 must match the value programmed into A1-05). The following

parameters cannot be viewed or edited until the value entered to A1-04 correctly matches the value set to A1-05: A1-01, A1-02,

A1-03, A1-06, and A2-01 through A2-33.

Note:

Parameter A1-05 is hidden from view. To display A1-05, access parameter A1-04 and press

OFF

and

simultaneously.

4.11 Verifying Parameter Settings and Backing Up Changes