C.7 BACnet Objects Supported

u

Present Value Access

The Present Value (PV) of BACnet objects can always be read. In addition, some PVs can be written or commanded. A

commandable PV is similar to writing the value, but the value is actually written into a priority array. The value occupying

the highest priority in the array will be used by the drive. The convention for showing how the PV is accessed is shown in

Table C.3

and will be noted for the PV of each object.

Table C.3 Present Value Access Values

PV Access

Name

Description

C

Commandable

Value written to a priority array. The highest priority value in the array is then written to the drive.

R

Readable

Value is read-only

W

Writable

Value written to the drive

u

Supported Properties of Objects

Table C.4 Object Properties

Property

Object Type

Device

Analog

Input

Analog

Output

Analog

Value

Binary

Output

Binary

Output

Binary

Value

Object_Identifier

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Object_Name

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Object_Type

Yes

Yes

Yes

Yes

Yes

Yes

Yes

System_Status

Yes

Vendor_Name

Yes

Vendor_Identifier

Yes

Model_Name

Yes

Firmware_Revision

Yes

Protocol_Version

Yes

Protocol_Revision

Yes

Protocol_Services_Supported

Yes

Protocol_Object_Types_Supported

Yes

Object_List

Yes

Max_ADPU_Length_Accepted

Yes

Segmentation_Supported

Yes

Local_Time

Yes

Local_Date

Yes

ADPU_Timeout

Yes

Number_Of_ADPU_Retries

Yes

Max_Masters

Yes

Max_Info_Frames

Yes

Device_Address_Binding

Yes

Database_Revision

Yes

Present_Value

Yes

Yes

Yes

Yes

Yes

Yes

Status_Flags

Yes

Yes

Yes

Yes

Yes

Yes

Event_State

Yes

Yes

Yes

Yes

Yes

Yes

Reliability

Yes

Yes

Yes

Yes

Yes

Yes

Out_Of_Service

Yes

Yes

Yes

Yes

Yes

Yes

Units

Yes

Yes

Yes

Priority_Array

Yes

<1>

Yes

<1>

Yes

Yes

Relinquish_Default

Yes

<1>

Yes

<1>

Yes

Yes

Polarity

Yes

Yes

C.7 BACnet Objects Supported