Yaskawa Z1000 AC Drive HVAC User Manual

Page 159

Advertising
background image

Setting 2: r/min

The setpoint and PI monitors are displayed in r/min with a resolution of 1 r/min.

Setting 3: User Defined

Parameters b5-38 and b5-39 determine the units and resolution used to display the values the setpoint in b5-19, and PI monitors

U5-01 and U5-04.

n

b5-21: PI Sleep Input Source

Selects the Sleep Function characteristic action. When b5-21 is set to 1, the Sleep Function Start Level (b5-15) is compared

to the output of the drive (Speed Command after PI Block). Use this setting for open loop control.
The Sleep Function Start Level (b5-15) can be compared to the drive input or setpoint by setting b5-21 to 0.
When b5-21 is set to 2, a variation of the Sleep Function called “Snooze” is enabled. See parameters b5-22 to b5-27 for details.

No.

Parameter Name

Setting Range

Default

b5-21

PI Sleep Input Source

0 to 2

1

Setting 0: PI Setpoint
Setting 1: SFS Input
Setting 2: Snooze

n

b5-22: PI Snooze Level

Sets the PI Snooze function start level as a percentage of maximum frequency.

No.

Parameter Name

Setting Range

Default

b5-22

PI Snooze Level

0 to 100%

0%

n

b5-23: PI Snooze Delay Time

Sets the PI Snooze function delay time in seconds.

No.

Parameter Name

Setting Range

Default

b5-23

PI Snooze Delay Time

0 to 2600 s

0 s

n

b5-24: PI Snooze Deactivation Level

When the PI feedback drops below this level, normal operation starts again. Sets as a percentage of maximum frequency.

No.

Parameter Name

Setting Range

Default

b5-24

PI Snooze Deactivation Level

0 to 100%

0%

n

b5-25: PI Setpoint Boost Setting

Temporary increase of PI setpoint to create an overshoot of the intended PI setpoint.

No.

Parameter Name

Setting Range

Default

b5-25

PI Setpoint Boost Setting

0 to 100%

0%

n

b5-26: PI Maximum Boost Time

Associated with the Snooze Function. In cases where the temporary PI Setpoint (intended PI setpoint + PI Setpoint Boost)

cannot be reached within the PI Maximum Boost Time (b5-26), the Setpoint Boost is interrupted and the Drive output is turned

off.

No.

Parameter Name

Setting Range

Default

b5-26

PI Maximum Boost Time

0 to 2600 s

0 s

n

b5-27: PI Snooze Feedback Level

The second method of initiating the Snooze Function. The drive output shuts off when the PI feedback level exceeds the PI

Snooze Feedback Level (b5-27).

4.13 Advanced Drive Setup Adjustments

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual

159

4

Start-Up Programming & Operation