European standards, Ce low voltage directive compliance, D.2 european standards – Yaskawa Z1000 AC Drive HVAC User Manual
Page 342: Area of use, Factory recommended branch circuit protection
D.2 European Standards
Figure D.1 CE Mark
The CE mark indicates compliance with European safety and environmental regulations. It is required for engaging in business
and commerce in Europe.
European standards include the Machinery Directive for machine manufacturers, the Low Voltage Directive for electronics
manufacturers, and the EMC guidelines for controlling noise.
This drive is in conformance with the Low Voltage Directive.
• Low Voltage Directive: 2006/95/EC
Devices used in combination with this drive must also be CE certified and display the CE mark. When using drives displaying
the CE mark in combination with other devices, it is ultimately the responsibility of the user to ensure compliance with CE
standards. After setting up the device, verify that conditions meet European standards.
u
CE Low Voltage Directive Compliance
This drive has been tested according to European standard IEC/EN 61800-5-1, and it fully complies with the Low Voltage
Directive.
To comply with the Low Voltage Directive, be sure to meet the following conditions when combining this drive with other
devices:
n
Area of Use
Do not use drives in areas with pollution higher than severity 2 and overvoltage category 3 in accordance with IEC/EN 664.
n
Factory Recommended Branch Circuit Protection
Yaskawa recommends installing one of the following types of branch circuit protection to maintain compliance with UL508C.
Semiconductor protective type fuses are preferred. Alternate branch circuit protection devices are also listed in
.
NOTICE: If a fuse is blown or a Ground Fault Circuit Interrupter (GFCI) is tripped, check the wiring and the selection of peripheral devices
to identify the cause. Contact Yaskawa before restarting the drive or the peripheral devices if the cause cannot be identified.
Table D.1 Factory Recommended Drive Branch Circuit Protection
Drive Model
Fuse Type
Manufacturer: Bussmann
Model
Fuse Ampere Rating (A)
Three-Phase 600 V Class
5A0003
FWP-50B
50
5A0004
FWP-50B
50
5A0006
FWP-60B
60
5A0009
FWP-60B
60
5A0011
FWP-70B
70
5A0017
FWP-100B
100
5A0022
FWP-100B
100
5A0027
FWP-125A
125
5A0032
FWP-125A
125
5A0041
FWP-175A
175
5A0052
FWP-175A
175
5A0062
FWP-250A
250
5A0077
FWP-250A
250
5A0099
FWP-250A
250
5A0125
FWP-350A
350
D.2 European Standards
342
YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual