2 general description – Yaskawa Z1000 AC Drive HVAC User Manual

Page 24

Advertising
background image

Motor Type

Induction Motors

Permanent Magnet Motors

Comments

Application-

Specific

Auto-Tuning

• Energy Saving Tuning
• Line to line resistance

• Stationary
• Line to line resistance

Automatically adjusts parameter settings that concern
electrical characteristics of the motor.

Speed Search

YES

YES

Bi-directional speed detection of a coasting motor to
restart it without stopping.

Energy-Saving Control

YES

Saves energy by always operating the motor at its
maximum efficiency.

High Slip Braking

YES

Increases motor loss to allow for faster deceleration.
Effectiveness may vary based on motor
characteristics.

Kinetic Energy Buffering

YES

YES

Decelerates the drive to allow it to ride through a
momentary power loss and continue operation.

Overexcitation Deceleration

YES

Allows faster deceleration without overvoltage trip.

Overvoltage Suppression

YES

YES

Prevents overvoltage by increasing speed during
regeneration.

1.2 General Description

24

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual