2 general description – Yaskawa Z1000 AC Drive HVAC User Manual
Page 24
Motor Type
Induction Motors
Permanent Magnet Motors
Comments
Application-
Specific
Auto-Tuning
• Energy Saving Tuning
• Line to line resistance
• Stationary
• Line to line resistance
Automatically adjusts parameter settings that concern
electrical characteristics of the motor.
Speed Search
YES
YES
Bi-directional speed detection of a coasting motor to
restart it without stopping.
Energy-Saving Control
YES
–
Saves energy by always operating the motor at its
maximum efficiency.
High Slip Braking
YES
–
Increases motor loss to allow for faster deceleration.
Effectiveness may vary based on motor
characteristics.
Kinetic Energy Buffering
YES
YES
Decelerates the drive to allow it to ride through a
momentary power loss and continue operation.
Overexcitation Deceleration
YES
–
Allows faster deceleration without overvoltage trip.
Overvoltage Suppression
YES
YES
Prevents overvoltage by increasing speed during
regeneration.
1.2 General Description
24
YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual