Device object – Yaskawa Z1000 AC Drive HVAC User Manual

Page 332

Advertising
background image

Object ID

Object Name

Modbus

Address

Active Text

Inactive Text

PV Access

BV35

Frequency Agree

002CH:bit 2

ON

OFF

R

BV36

Desired Frequency Agree

002CH:bit 3

ON

OFF

R

BV37

Frequency Detect 1

002CH:bit 4

ON

OFF

R

BV38

Frequency Detect 2

002CH:bit 5

ON

OFF

R

BV39

Drive Startup Complete

002CH:bit 6

ON

OFF

R

BV40

Low Voltage Detect

002CH:bit 7

ON

OFF

R

BV41

Base Block

002CH:bit 8

ON

OFF

R

BV42

Frequency Reference Mode

002CH:bit 9

COM

LOCAL

R

BV43

Run Command Mode

002CH:bit 10

COM

LOCAL

R

BV44

Overtorque Detect

002CH:bit 11

ON

OFF

R

BV45

Frequency Refer Lost

002CH:bit 12

ON

OFF

R

BV46

Retry Error

002CH:bit 13

ON

OFF

R

BV47

Modbus Comms Error

002CH:bit 14

ON

OFF

R

BV48

Modbus Timeout Error

002CH:bit 15

ON

OFF

R

BV49

CRC Error

003DH:bit 0

ON

OFF

R

BV50

Invalid Data Length

003DH:bit 1

ON

OFF

R

BV51

Parity Error

003DH:bit 3

ON

OFF

R

BV52

Overrun Error

003DH:bit 4

ON

OFF

R

BV53

Framing Error

003DH:bit 5

ON

OFF

R

BV54

Timeout Error

003DH:bit 6

ON

OFF

R

BV55

<1>

Parameter Accept

0910H:bit 0

ON

OFF

W

BV56

<1>

Parameter Enter

0900H:bit 0

ON

OFF

W

BV57

Drive Comm Error

-

ON

OFF

R

<1>

Refer to Accessing Drive Parameters and the Enter Command on page 333

for an explanation of how to read and write drive parameters not

listed in the analog or binary objects.

u

Device Object

The Device Object fully describes the BACnet device to the network. Notable is that the Device Object Instance ID and the

Device Object Name are configurable.
The Device Object Instance ID is a unique internetwork-wide numerical value. It is a 22-bit value that can range from 0 to

4,194,303. It is configurable by parameters H5-14 and H5-15. Any changes to these parameters will not take effect until the

power is cycled to the drive.
The Device Object Name is a unique internetwork-wide character string. It is a 20-character string. It is writable from the

BACnet network. Any new string written will not take effect until the power is cycled to the drive.

C.7 BACnet Objects Supported

332

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual