2.2 Mechanical Installation

This section outlines specifications, procedures, and the environment for proper mechanical installation of the drive.

u

Installation Environment

Install the drive in an environment matching the specifications in

Table 2.1

to help prolong the optimum performance life of

the drive.

Table 2.1 Installation Environment

Environment

Conditions

Installation Area

Indoors

Ambient Temperature

IP20/NEMA Type 1 enclosure: -10 °C to +40 °C (14 °F to 104 °F)

IP00/Open Type enclosure: -10 °C to +50 °C (14 °F to 122 °F)

Drive reliability improves in environments without wide temperature fluctuations.

When using the drive in an enclosure panel, install a cooling fan or air conditioner in the area to ensure that the air

temperature inside the enclosure does not exceed the specified levels.

Do not allow ice to develop on the drive.

Humidity

95% RH or less and free of condensation

Storage Temperature

-20 °C to +60 °C (-4 °F to +104 °F)

Surrounding Area

Install the drive in an area free from:
• oil mist and dust
• metal shavings, oil, water, or other foreign materials
• radioactive materials
• combustible materials (e.g., wood)
• harmful gases and liquids
• excessive vibration
• chlorides
• direct sunlight.

Altitude

1000 m (3281 ft.) or lower, up to 3000 m (9843 ft.) with derating

Vibration

10 to 20 Hz at 9.8 m/s

2

(32.15 ft/s

2

)

20 to 55 Hz at 5.9 m/s

2

(19.36 ft/s

2

) (Models 5A0003 to 5A0099) or

2.0 m/s

2

(6.56 ft/s

2

) (Models 5A0125 to 5A0242)

Orientation

Install the drive vertically to maintain maximum cooling effects.

NOTICE: Avoid placing drive peripheral devices, transformers, or other electronics near the drive as the noise created can lead to erroneous

operation. If such devices must be used in close proximity to the drive, take proper steps to shield the drive from noise.

NOTICE: Prevent foreign matter such as metal shavings and wire clippings from falling into the drive during installation. Failure to comply

could result in damage to the drive. Place a temporary cover over the top of the drive during installation. Remove the temporary cover before

drive start-up, as the cover will reduce ventilation and cause the drive to overheat.

u

Installation Orientation and Spacing

Install the drive upright as illustrated in

Figure 2.1

to maintain proper cooling.

Figure 2.1 Correct Installation Orientation

NOTICE: Install the drive upright as specified in the manual. Failure to comply may damage the drive due to improper cooling.