Attempted to use a function that is not valid for the selected control mode. Check the motor control method and the functions available.

In OLV/PM, parameters E5-02 to E5-07 are set to 0.

• Set the correct motor code in accordance with the motor being used

(E5-01).

• When using a special-purpose motor, set E5- in accordance with the

test report provided.

The following settings have occurred in OLV/PM:
• E5-03 does not equal 0
• E5-09 and E5-24 are both equal to 0, or neither equals 0

• Set E5-09 or E5-24 to the correct value, and set the other to 0.
• Set the motor rated current for PM to 0 (E5-03).

Note:

Use U1-18 to find parameters that are set outside the specified setting range. When multiple errors occur simultaneously, other errors are

given precedence over oPE08.

Digital Operator Display

Error Name

oPE09

PID Control Selection Fault
PID control function selection is incorrect. Requires that PID control is

enabled (b5-01 = 1 to 4).

Cause

Possible Solutions

The following simultaneous contradictory settings have occurred:
• b5-15 is not set to 0.0 (PID Sleep Function Operation Level)
• The stopping method is set to either DC Injection Braking or coast to stop

with a timer (b1-03 = 2 or 3).

• Set b5-15 to a value other than 0.0.
• Set the stopping method to coast to stop or ramp to stop (b1-03 = 0 or 1).

b5-01 is set to 1 or 2, enabling PID control, but the lower limit for the

frequency reference (d2-02) is not set to 0 while reverse output is enabled

(b5-11 = 1).

Correct the parameter settings.

b5-01 is set to 3 or 4, enabling PID control, but the lower limit for the

frequency reference (d2-01) is not 0.

Correct the parameter settings.

Digital Operator Display

Error Name

oPE10

V/f Data Setting Error
One of the following setting errors has occurred:

E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04

Cause

Possible Solutions

V/f pattern setting error.

Correct the settings for E1-04, E1-06, E1-07, E1-09, and E1-11.

Digital Operator Display

Error Name

oPE11

Carrier Frequency Setting Error
Correct the setting for the carrier frequency.

Cause

Possible Solutions

The following simultaneous contradictory settings have occurred: C6-05 >

6 and C6-04 > C6-03 (carrier frequency lower limit is greater than the upper

limit).

If C6-05 ≤ 6, the drive operates at C6-03.

Correct the parameter settings.

The upper and lower limits between C6-02 and C6-05 are contradictory.

HOA Keypad Display

Error Name

oPE16

Energy Saving Constants Error

Cause

Possible Solutions

The following contradictory settings are true:

A1-02 = 0, S1-01 =1, and b8-01 = 1

Correct the parameter settings.

HOA Keypad Display

Error Name

oPE27

BP Program Error
Bypass mode is not correctly configured.

Cause

Possible Solutions

5.6 Programming Errors

220