C.1 BACnet Configuration

Drives can be monitored and controlled by a controller on a Building Automation and Control network (BACnet) using RS-485

technology and MS-TP (Master-Slave/Token-Passing) protocol. The drives conform to the BACnet application specific

controller (B-ASC) device profile.
Up to 127 drives can communicate on a single BACnet MS-TP network. If more drives or BACnet devices are required, then

a BACnet router is required to allow another MS-TP network to be available with up to another 127 drives.
The BACnet node address is configurable by a parameter in the drive. This defines the physical address of the drive on the

MS-TP network. In addition, both the Device Object instance ID and the Device Object Name are configurable. These allow

the drive to have a virtual address, thus simplifying controller configuration.
Once the addressing is set, a controller can initiate communication to the drive. The drive will perform the specified function

and then send a response back to the controller. The drive will usually respond immediately, but may delay its response until

it gets the token for commands that may take extra local processing time.

BACnet

Workstation

Drive Drive Drive

MS-TP

BACnet over Ethernet

Router

Router

Drive Drive Drive

MS-TP

Figure C.1 Connecting Multiple Drives to a BACnet Workstation

C.1 BACnet Configuration

318

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual