Yaskawa Z1000 AC Drive HVAC User Manual

Page 204

Advertising
background image

The option card installed into port CN5-A is

incompatible with the drive

Check if the drive supports the option card to be installed. Contact Yaskawa for assistance.

Digital Operator Display

Fault Name

oFA01

Option Card Fault at Option Port CN5-A
Option not properly connected

Cause

Possible Solution

The option card connection to port CN5-A is

faulty

• Turn off the power and reconnect the option card.
• Check if the option card is properly plugged into the option port. Make sure the card is fixed properly.
• If the option is not a communication option card, try to use the card in a different option port. If the

option card works properly in a different option port, CN5-A is damaged, and the drive requires

replacement. If the error persists (oFb01 or oFC01 occur), replace the option card.

Digital Operator Display

Fault Name

to

oFA03 to oFA06

Option Card Error Occurred at Option Port CN5-A

,

oFA10, oFA11

to

oFA12 to oFA17

Option Card Connection Error (CN5-A)

to

oFA30 to oFA43

Communication Option Card Connection Error (CN5-A)

Cause

Possible Solution

Option card or hardware is damaged

• Cycle power to the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa

representative for instructions on replacing the control board.

Digital Operator Display

Fault Name

oH

Heatsink Overheat
The heatsink temperature exceeded the overheat pre-alarm level set to L8-02. The default value for L8-02

is determined by drive capacity (o2-04).

Cause

Possible Solution

Surrounding temperature is too high

• Check the temperature surrounding the drive. Verify temperature is within drive specifications.
• Improve the air circulation within the enclosure panel.
• Install a fan or air conditioner to cool the surrounding area.
• Remove anything near the drive that might be producing excessive heat.

Load is too heavy

• Measure the output current.
• Decrease the load.
• Lower the carrier frequency (C6-02).

Internal cooling fan is stopped

• Replace the cooling fan.
• After replacing the cooling fan, set parameter o4-03 to 0 to reset the cooling fan maintenance.

Digital Operator Display

Fault Name

oH1

Overheat 1 (Heatsink Overheat)
The heatsink temperature exceeded the drive overheat level. Overheat level is determined by drive

capacity (o2-04).

Cause

Possible Solution

Surrounding temperature is too high

• Check the temperature surrounding the drive.
• Improve the air circulation within the enclosure panel.
• Install a fan or air conditioner to cool the surrounding area.
• Remove anything near the drive that might be producing excessive heat.

Load is too heavy

• Measure the output current.
• Lower the carrier frequency (C6-02).
• Reduce the load.

HOA Keypad Display

Minor Fault Name

oH3

Motor Overheat
The motor overheat signal entered to a multi-function analog input terminal exceeded the alarm level

(H3-02 or H3-10 = E).

Cause

Possible Solutions

Motor thermostat wiring is faulty (PTC input).

Repair the PTC input wiring.

5.4 Fault Detection