Yaskawa Z1000 AC Drive HVAC User Manual
Page 204
The option card installed into port CN5-A is
incompatible with the drive
Check if the drive supports the option card to be installed. Contact Yaskawa for assistance.
Digital Operator Display
Fault Name
oFA01
Option Card Fault at Option Port CN5-A
Option not properly connected
Cause
Possible Solution
The option card connection to port CN5-A is
faulty
• Turn off the power and reconnect the option card.
• Check if the option card is properly plugged into the option port. Make sure the card is fixed properly.
• If the option is not a communication option card, try to use the card in a different option port. If the
option card works properly in a different option port, CN5-A is damaged, and the drive requires
replacement. If the error persists (oFb01 or oFC01 occur), replace the option card.
Digital Operator Display
Fault Name
to
oFA03 to oFA06
Option Card Error Occurred at Option Port CN5-A
,
oFA10, oFA11
to
oFA12 to oFA17
Option Card Connection Error (CN5-A)
to
oFA30 to oFA43
Communication Option Card Connection Error (CN5-A)
Cause
Possible Solution
Option card or hardware is damaged
• Cycle power to the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
Digital Operator Display
Fault Name
oH
Heatsink Overheat
The heatsink temperature exceeded the overheat pre-alarm level set to L8-02. The default value for L8-02
is determined by drive capacity (o2-04).
Cause
Possible Solution
Surrounding temperature is too high
• Check the temperature surrounding the drive. Verify temperature is within drive specifications.
• Improve the air circulation within the enclosure panel.
• Install a fan or air conditioner to cool the surrounding area.
• Remove anything near the drive that might be producing excessive heat.
Load is too heavy
• Measure the output current.
• Decrease the load.
• Lower the carrier frequency (C6-02).
Internal cooling fan is stopped
• Replace the cooling fan.
• After replacing the cooling fan, set parameter o4-03 to 0 to reset the cooling fan maintenance.
Digital Operator Display
Fault Name
oH1
Overheat 1 (Heatsink Overheat)
The heatsink temperature exceeded the drive overheat level. Overheat level is determined by drive
capacity (o2-04).
Cause
Possible Solution
Surrounding temperature is too high
• Check the temperature surrounding the drive.
• Improve the air circulation within the enclosure panel.
• Install a fan or air conditioner to cool the surrounding area.
• Remove anything near the drive that might be producing excessive heat.
Load is too heavy
• Measure the output current.
• Lower the carrier frequency (C6-02).
• Reduce the load.
HOA Keypad Display
Minor Fault Name
oH3
Motor Overheat
The motor overheat signal entered to a multi-function analog input terminal exceeded the alarm level
(H3-02 or H3-10 = E).
Cause
Possible Solutions
Motor thermostat wiring is faulty (PTC input).
Repair the PTC input wiring.
5.4 Fault Detection
204
YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual