A2: User Parameters

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

A2-01 to

A2-32

(106 to

125)

User Parameters 1 to

32

User Param 1 - 32

Recently edited parameters are listed here. The user can also

select parameters to appear here for quicker access.

Default:

<1>

Range: A1-00 to

S6-07

A2-33

(126)

User Parameter

Automatic Selection

User Parms Sel

0: Disabled

1: Enabled

0: Parameters A2-01 to A2-32 are reserved for the user to create

a list of User Parameters.

1: Save history of recently viewed parameters.

Recently edited parameters will be saved to A2-17 through

A2-32 for quicker access.

Default: 1

<2>

Range: 0, 1

<1> Default setting value is dependent on the Application Preset selected with parameter A1-06.
<2> Default setting value is dependent on parameter A1-06. Default is 0 when A1-06 = 0, and 1 when A1-06 ≠ 0.

B.1 A: Initialization Parameters

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual

263