Flowchart A: Basic Start-Up and Motor Tuning

Flowchart A in

Figure 4.9

describes a basic start-up sequence that varies slightly depending on the application. Use the drive

default parameter settings in simple applications that do not require high precision.

YES

NO

START

Install and wire the drive as explained in Chapters 1, 2, and 3

Apply main power on to the drive

Adhere to safety messages concerning application of power

Application Presets

A1-06 used ?

Set the control mode in parameter A1-02.

Refer to
Application
Selection section

To

Flowchart A-1

Control Mode

A1-02 =

To

Flowchart A-2

Set the basic parameters

b1-01/02 for frequency reference and run command source selection

H1-, H2-, H3-, H4- for I/O terminal setting

d1- for multi-speed references if used

C1- and C2- for accel./decel. and S-curve time settings

Fine tune parameters. Adjust application settings (PI, ...) if necessary.

Check the machine operation and verify parameter settings.

Drive is ready to run the application.

From Flowchart A-1 or A-2

0: V/f

5: OLV/PM

E1-01 for input voltage setting

Figure 4.9 Basic Start-Up

Note:

1. Execute Stationary Auto-Tuning for Line-to-Line Resistance if the drive has been Auto-Tuned and then moved to a different location

where the motor cable length exceeds 50 m.

2. Perform Auto-Tuning again after installing an AC reactor or other such components to the output side of the drive.

4.4 Start-Up Flowcharts