D3: jump frequency, D4: frequency reference hold function, D6: field weakening – Yaskawa Z1000 AC Drive HVAC User Manual

Page 273

Advertising
background image

u

d3: Jump Frequency

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

d3-01

(294)

Jump Frequency 1

Jump Freq 1

Eliminates problems with resonant vibration of the motor/

machine by avoiding continuous operation in predefined

frequency ranges. The drive accelerates and decelerates the

motor through the prohibited frequency ranges.

Setting 0.0 disables this function.

Parameters must be set so that d3-01 ≥ d3-02 ≥ d3-03.

Default: 0.0 Hz

Min.: 0.0

Max.: 240.0

165

d3-02

(295)

Jump Frequency 2

Jump Freq 2

Eliminates problems with resonant vibration of the motor/

machine by avoiding continuous operation in predefined

frequency ranges. The drive accelerates and decelerates the

motor through the prohibited frequency ranges.

Setting 0.0 disables this function.

Parameters must be set so that d3-01 ≥ d3-02 ≥ d3-03.

Default: 0.0 Hz

Min.: 0.0

Max.: 240.0

165

d3-03

(296)

Jump Frequency 3

Jump Freq 3

Eliminates problems with resonant vibration of the motor/

machine by avoiding continuous operation in predefined

frequency ranges. The drive accelerates and decelerates the

motor through the prohibited frequency ranges.

Setting 0.0 disables this function.

Parameters must be set so that d3-01 ≥ d3-02 ≥ d3-03.

Default: 0.0 Hz

Min.: 0.0

Max.: 240.0

165

d3-04

(297)

Jump Frequency Width Jump Bandwidth

Sets the dead-band width around each selected prohibited

frequency reference point.

Default: 1.0 Hz

Min.: 0.0

Max.: 20.0

165

u

d4: Frequency Reference Hold Function

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

d4-01

(298)

Frequency Reference

Hold Function Selection

Fref Hold Sel

0: Disabled

1: Enabled

0: Disabled.

Drive starts from zero when the power is switched on.

1: Enabled.

At power up, the drive starts the motor at the Hold frequency

that was saved.

Default: 0

Range: 0, 1

d4-10

(2B6)

Up/Down Frequency

Reference Limit

Selection

Up/Dn LowLim Sel

0: D2-02 or Analog

1: D2-02 Only

0: The lower limit is determined by d2-02 or an analog input.

1: The lower limit is determined by d2-02.

Default: 0

Range: 0, 1

u

d6: Field Weakening

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

d6-01

(2A0)

Field Weakening Level Field-Weak Lvl

Sets the drive output voltage for the Field Weakening function

as a percentage of the maximum output voltage. Enabled when

a multi-function input is set for Field Weakening

(H1- = 63).

Default: 80%

Min.: 0

Max.: 100

d6-02

(2A1)

Field Weakening

Frequency Limit

Field-Weak Freq

Sets the lower limit of the frequency range where Field

Weakening control is valid. The Field Weakening command is

valid only at frequencies above this setting and only when the

output frequency matches the frequency reference (speed

agree).

Default: 0.0 Hz

Min.: 0.0

Max.: 240.0

B.4 d: References

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual

273

B

Parameter List

Advertising