H1 Multi-Function Digital Input Selections

H1-

Setting

Function

LCD Display

Description

Page

7B

KEB Ride-Thru 2 (N.O.) KEB Ridethru2NO

Closed: KEB Ride-Thru 2 enabled. Drive disregards L2-29 and performs Single

Drive KEB Ride-Thru 2.

7C

Short circuit braking

(N.O.)

SC Brake (NO)

Closed: Short Circuit Braking enabled

7D

Short circuit braking

(N.C.)

SC Brake (NC)

OLV/PM

OLV/PM

Open: Short Circuit Braking enabled

A4

BP Customer Safeties

BP Emg Override

Closed: Indicates that customer safeties are in place.

A5

BP Drive/Bypass Select BP Drv/Bypss Sel

Open: Bypass mode.

Closed: Drive mode.

A6

BP BAS Interlock Input BP BAS Interlock

Closed: Indicates that the dampers are open

A7

BP Customer Safeties

BP Cust Safeties

Closed: Indicates that customer safeties are in place.

A8

Secondary PI Disable

(N.O.)

PI2 Disable N.O.

Closed: Disables the secondary PI controller. Output behavior depends on the

setting of S3-12.

A9

Secondary PI Disable

(N.C.)

PI2 Disable N.C.

Closed: Enables the secondary PI controller. Output behavior depends on the

setting of S3-12 when open.

AA

Secondary PI Inverse

Operation

PI2 Invert

Closed: Changes the sign of the secondary PI controller input (reverse acting PI

control).

AB

Secondary PI Integral

Reset

PI2 Intgrl Reset

Closed: Resets the secondary PI controller integral value.

AC

Secondary PI Integral

Hold

PI2 Intgrl Hold

Closed: Locks the value of the secondary PI controller integral value.

AD

Select Secondary PI

Parameters

Select PI2 Parms

Closed: Uses the secondary PI controller Proportional and Integral adjustments

(S3-06 and S3-07) instead of the primary PI controller Proportional and Integral

adjustments (b5-02 and b5-03). Only valid when S3-01 = 0 (secondary PI

controller disabled).

Note:

This multi-function input has no effect on the secondary PI

controller. It is only used for the primary PI controller (b5-).

AE

BP Bypass Run

BP Bypass Run

Closed: Commands a Run (via closing the BP Bypass Relay multi-function output)

when in Bypass mode.

AF

Emergency Override

Forward Run

EmergOverrideFWD Closed: Emergency Override Forward Run

B0

Emergency Override

Reverse Run

EmergOverrideREV

Closed: Emergency Override Reverse Run

B1

Customer Safeties

CustomerSafeties

The functionality is identical to Drive Enable 2 (H1- = 70), except for the

following characteristics:
• The stopping method is forced to Coast to Stop when the input is open
• The drive will display a “SAFE” alarm if the input is open when a Run command

is present. It will not display “dnE”.

Open: Customer Safeties are open. Drive will not run. Stopping method is Coast

to Stop.

Closed: Customer Safeties are in place.

B2

BAS Interlock

BAS Interlock

Open: Damper interlock is not closed. Drive output is shut off (baseblocked). The

drive displays an "inTLK" message if a Run command is present. It will not display

"dnE".

Closed: Damper interlock is closed. Drive operates normally.

Note:

The state of the BAS Interlock multi-function input has no effect on

the Emergency Override multi-function inputs (H1- = AF, B0).

The Emergency Override command is accepted when the BAS

Interlock digital input is open or closed.

B.7 H Parameters: Multi-Function Terminals

284