B.9 n: Special Adjustment

The n parameters adjust more advanced performance characteristics such as Hunting Prevention, speed feedback detection,

High Slip Braking, and Online Tuning for motor line-to-line resistance.

u

n1: Hunting Prevention

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

n1-01

(580)

Hunting Prevention

Selection

Hunt Prev Select

0: Disabled

1: Enabled

0: Disabled

1: Enabled

Default: 1

Range: 0, 1

n1-02

(581)

Hunting Prevention

Gain Setting

Hunt Prev Gain

If the motor vibrates while lightly loaded, increase the gain by

0.1 until vibration ceases. If the motor stalls, decrease the gain

by 0.1 until the stalling ceases.

Default: 1.00

Min.: 0.00

Max.: 2.50

n1-03

(582)

Hunting Prevention

Time Constant

Hunt Prev Time

Sets the time constant used for Hunting Prevention.

Default:

<1>

Min.: 0 ms

Max.: 500 ms

n1-05

(530)

Hunting Prevention

Gain while in Reverse

Hprev Gain @Rev

Sets the gain used for Hunting Prevention. If set to 0, the gain

set to n1-02 is used for operation in reverse.

Default: 0.00

Min.: 0.00

Max.: 2.50

<1> Default setting is dependent on parameter o2-04, Drive Model Selection.

u

n3: High Slip Braking (HSB) and Overexcitation Braking

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

n3-01

(588)

High-Slip Braking

Deceleration Frequency

Width

HSB DecStepWidth

Sets the output frequency reduction step width for when the

drive stops the motor using HSB. Set as a percentage of the

maximum output frequency. Increase this setting if overvoltage

occurs during HSB.

Default: 5%

Min.: 1

Max.: 20

n3-02

(589)

High-Slip Braking

Current Limit

HSB Current Lim

Sets the current limit during HSB as a percentage of the motor

rated current.

Default:

<1>

Min.: 0%

Max.: 200%

n3-03

(58A)

High-Slip Braking

Dwell Time at Stop

HSB DwelTim@Stp

Sets the time the drive will run with minimum frequency

(E1-09) at the end of deceleration.

If this time is set too low, the machine inertia can cause the

motor to rotate slightly after HSB.

Default: 1.0 s

Min.: 0.0

Max.: 10.0

n3-04

(58B)

High-Slip Braking

Overload Time

HSB OL Time

Sets the time required for an HSB overload fault (oL7) to occur

when the drive output frequency does not change during an

HSB stop. This parameter does not typically require

adjustment.

Default: 40 s

Min.: 30

Max.: 1200

n3-13

(531)

Overexcitation

Deceleration Gain

Hflux Brake Gain

Sets the gain applied to the V/f pattern during Overexcitation

Deceleration (L3-04 = 4).

Default: 1.10

Min.: 1.00

Max.: 1.40

n3-21

(579)

High-Slip Suppression

Current Level

Hflux I Supp Lvl

Sets output current level at which the drive will start reducing

the overexcitation gain in order to prevent a too high motor slip

during Overexcitation Deceleration. Set as a percentage of the

drive rated current.

Default: 100%

Min.: 0

Max.: 150

n3-23

(57B)

Overexcitation

Operation Selection

Hflux Brake Sel

0: Enabled-Both Dir

1: Enabled-Fwd only

2: Enabled-Rev only

0: Enabled in both directions

1: Enabled only when rotating forward

2: Enabled only when in reverse

Default: 0

Range: 0 to 2

<1> Default setting is dependent on parameter L8-38, Frequency Reduction Selection.

B.9 n: Special Adjustment

296