Grounding, Ce standards compliance for dc power supply input, Guarding against harmful materials – Yaskawa Z1000 AC Drive HVAC User Manual

Page 343

Advertising
background image

Drive Model

Fuse Type

Manufacturer: Bussmann

Model

Fuse Ampere Rating (A)

5A0145

FWP-350A

350

5A0192

FWP-600A

600

5A0242

FWP-600A

600

n

Grounding

The drive is designed to be used in T-N (grounded neutral point) networks. If installing the drive in other types of grounded

systems, contact your Yaskawa representative for instructions.

n

CE Standards Compliance for DC Power Supply Input

Install the fuses in the following tables to meet CE standards.

M

M

W/T3

Drive

V/T2

U/T1

+1

_

W/T3

Drive

V/T2

U/T1

+1

_

+

_

Fuse

Fuse

DC power supply

(converter)

Figure D.2 Example of DC Power Supply Input (Two Drives Connected in Series)

Note:

1. When connecting multiple drives together, make sure that each drive has its own fuse. Replace all fuses when one fuse blows.
2.

Refer to Standard Connection Diagram on page 70

for an AC power supply.

3. The recommended fuses and fuse holders are made by Fuji Electric.

n

Guarding Against Harmful Materials

When installing IP00/Open Type enclosure drives, use an enclosure that prevents foreign material from entering the drive

from above or below.

D.2 European Standards

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual

343

D

Standards Compliance

Advertising