Grounding, Ce standards compliance for dc power supply input, Guarding against harmful materials – Yaskawa Z1000 AC Drive HVAC User Manual
Page 343
Drive Model
Fuse Type
Manufacturer: Bussmann
Model
Fuse Ampere Rating (A)
5A0145
FWP-350A
350
5A0192
FWP-600A
600
5A0242
FWP-600A
600
n
Grounding
The drive is designed to be used in T-N (grounded neutral point) networks. If installing the drive in other types of grounded
systems, contact your Yaskawa representative for instructions.
n
CE Standards Compliance for DC Power Supply Input
Install the fuses in the following tables to meet CE standards.
M
M
W/T3
Drive
V/T2
U/T1
+1
_
W/T3
Drive
V/T2
U/T1
+1
_
+
_
Fuse
Fuse
DC power supply
(converter)
Figure D.2 Example of DC Power Supply Input (Two Drives Connected in Series)
Note:
1. When connecting multiple drives together, make sure that each drive has its own fuse. Replace all fuses when one fuse blows.
2.
Refer to Standard Connection Diagram on page 70
3. The recommended fuses and fuse holders are made by Fuji Electric.
n
Guarding Against Harmful Materials
When installing IP00/Open Type enclosure drives, use an enclosure that prevents foreign material from entering the drive
from above or below.
D.2 European Standards
YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual
343