T: motor tuning, T1: induction motor auto-tuning, T2: pm motor auto-tuning – Yaskawa Z1000 AC Drive HVAC User Manual

Page 307: B.12 t: motor tuning

Advertising
background image

B.12 T: Motor Tuning

Enter data into the following parameters to tune the motor and drive for optimal performance.

u

T1: Induction Motor Auto-Tuning

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

T1-01

(701)

<1>

Auto-Tuning Mode

Selection

Tuning Mode Sel

2: Term Resistance

3: On-

DelayCompTune

2: Stationary Auto-Tuning for Line-to-Line Resistance

3: Rotational Auto-Tuning for V/f Control Energy Saving

Default: 2

Range: 2, 3

140

T1-02

(702)

Motor Rated Power

Mtr Rated Power

Sets the motor rated power as specified on the motor nameplate.

Note:

Use the following formula to convert horsepower

into kilowatts: 1HP = 0.746 kW.

Default:

<2>

Min.: 0.00 kW

Max.: 650.00

kW

140

T1-03

(703)

Motor Rated Voltage

Rated Voltage

Sets the motor rated voltage as specified on the motor nameplate. Default: 575.0

V

Min: 0.0

Max: 733.1

140

T1-04

(704)

Motor Rated Current

Rated Current

Sets the motor rated current as specified on the motor nameplate. Default:

<2>

Min.: 10% of

drive rated

current

Max.: 200% of

drive rated

current

141

T1-05

(705)

Motor Base Frequency Rated Frequency

Sets the rated frequency of the motor as specified on the motor

nameplate.

Default: 60.0

Hz

Min.: 0.0

Max.: 240.0

141

T1-06

(706)

Number of Motor Poles Number of Poles

Sets the number of motor poles as specified on the motor

nameplate.

Default: 4

Min.: 2

Max.: 48

141

T1-07

(707)

Motor Base Speed

Rated Speed

Sets the rated speed of the motor as specified on the motor

nameplate.

Default: 1750 r/

min

Min.: 0

Max.: 14400

141

T1-11

(70B)

Motor Iron Loss

Mtr Iron Loss(W)

Sets the iron loss for determining the Energy Saving coefficient.

The value is set to E2-10 (motor iron loss) set when the power is

cycled. If T1-02 is changed, a default value appropriate for the

motor capacity that was entered will appear.

Default: 14 W

<3>

Min.: 0

Max.: 65535

141

T1-12

(FFF0) T1 Tuning Start

Tuning Ready

The drive starts tuning.

No setting

available

141

<1> The availability of certain Auto-Tuning methods depends on the control mode selected for the drive.
<2> Default setting is dependent on parameter o2-04, Drive Model Selection.
<3> Default setting value differs depending on the motor code value and motor parameter settings.

u

T2: PM Motor Auto-Tuning

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

T2-01

(750)

PM Motor Auto-Tuning

Mode Selection

PM Tuning Mode

0: Standard Tuning

OLV/PM

OLV/PM

0: PM Motor Parameter Settings

Default: 0

Range: 0

T2-03

(752)

PM Motor Type

PM Motor Type

0: IPM motor

1: SPM motor

OLV/PM

OLV/PM

0: IPM motor

1: SPM motor

Default: 1

Range: 0, 1

T2-04

(730)

PM Motor Rated Power Mtr Rated Power

OLV/PM

OLV/PM

Sets the motor rated power.

Note:

Use the following formula to convert horsepower

into kilowatts: 1 HP = 0.746 kW.

Default:

<1>

Min.: 0.00 kW

Max.: 650.00

kW

B.12 T: Motor Tuning

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual

307

B

Parameter List