13 advanced drive setup adjustments, Setting specification characteristic application f, Table 4.28 high starting torque, settings 8 to b – Yaskawa Z1000 AC Drive HVAC User Manual

Page 167: Table 4.29 rated output operation, settings c to f

Advertising
background image

Setting

Specification

Characteristic

Application

F

<1>

60 Hz

Variable torque

Used for variable torque applications. The default setting is

the same as V/f pattern Setting 7.

<1> Setting F enables a custom V/f pattern by changing parameters E1-04 to E1-13. When the drive is shipped, the default values for parameters E1-04

to E1-13 are equal to predefined V/f pattern 1.

The following tables show details on predefined V/f patterns.

Predefined V/f Patterns for Models 5A0003 to 5A0009

Table 4.26 Constant Torque Characteristics, Settings 0 to 3

Setting = 0

50 Hz

Setting = 1

60 Hz

Setting = 2

60 Hz

Setting = 3

72 Hz

0

25.9

575

1.3 2.5

50

43.1

V

oltage (V)

Frequency (Hz)

0

25.9

43.1

575

1.5 3

60

V

oltage (V)

Frequency (Hz)

0

25.9

43.1

575

1.5 3

60

50

V

oltage (V)

Frequency (Hz)

0

25.9

43.1

575

1.5 3

72

60

V

oltage (V)

Frequency (Hz)

Table 4.27 Derated Torque Characteristics, Settings 4 to 7

Setting = 4

50 Hz

Setting = 5

50 Hz

Setting = 6

60 Hz

Setting = 7

60 Hz

0

23.0

575

1.3

25

50

100.6

V

oltage (V)

Frequency (Hz)

0

25.9

575

1.3

25

50

143.8

V

oltage (V)

Frequency (Hz)

0

23.0

575

1.5

30

60

100.6

V

oltage (V)

Frequency (Hz)

0

25.9

575

1.5

30

60

143.8

V

oltage (V)

Frequency (Hz)

Table 4.28 High Starting Torque, Settings 8 to B

Setting = 8

50 Hz

Setting = 9

50 Hz

Setting = A

60 Hz

Setting = B

60 Hz

0

31.6

575

1.3 2.5

50

54.6

V

oltage (V)

Frequency (Hz)

0

37.4

575

1.3 2.5

50

69.0

V

oltage (V)

Frequency (Hz)

0

31.6

575

1.5 3

60

54.6

V

oltage (V)

Frequency (Hz)

0

43.1

575

1.5 3

60

69.0

V

oltage (V)

Frequency (Hz)

Table 4.29 Rated Output Operation, Settings C to F

Setting = C

90 Hz

Setting = D

120 Hz

Setting = E

180 Hz

Setting = F

60 Hz

0

25.9

43.1

575

1.5 3

90

60

V

oltage (V)

Frequency (Hz)

0

25.9

43.1

575

1.5 3

120

60

V

oltage (V)

Frequency (Hz)

0

25.9

43.1

575

1.5 3

180

60

V

oltage (V)

Frequency (Hz)

0

25.9

43.1

575

1.5 3

60

V

oltage (V)

Frequency (Hz)

Predefined V/f Patterns for Models 5A0011 to 5A0077

Table 4.30 Rated Torque Characteristics, Settings 0 to 3

Setting = 0

50 Hz

Setting = 1

60 Hz

Setting = 2

60 Hz

Setting = 3

72 Hz

0

20.1

575

1.3 2.5

50

40.3

V

oltage (V)

Frequency (Hz)

0

20.1

40.3

575

1.5 3

60

V

oltage (V)

Frequency (Hz)

V

oltage (V)

Frequency (Hz)

0

20.1

40.3

575

1.5 3

60

50

0

20.1

40.3

230

1.5 3

72

60

V

oltage (V)

Frequency (Hz)

4.13 Advanced Drive Setup Adjustments

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual

167

4

Start-Up Programming & Operation