13 advanced drive setup adjustments, Setting specification characteristic application f, Table 4.28 high starting torque, settings 8 to b – Yaskawa Z1000 AC Drive HVAC User Manual
Page 167: Table 4.29 rated output operation, settings c to f
Setting
Specification
Characteristic
Application
F
<1>
60 Hz
Variable torque
Used for variable torque applications. The default setting is
the same as V/f pattern Setting 7.
<1> Setting F enables a custom V/f pattern by changing parameters E1-04 to E1-13. When the drive is shipped, the default values for parameters E1-04
to E1-13 are equal to predefined V/f pattern 1.
The following tables show details on predefined V/f patterns.
Predefined V/f Patterns for Models 5A0003 to 5A0009
Table 4.26 Constant Torque Characteristics, Settings 0 to 3
Setting = 0
50 Hz
Setting = 1
60 Hz
Setting = 2
60 Hz
Setting = 3
72 Hz
0
25.9
575
1.3 2.5
50
43.1
V
oltage (V)
Frequency (Hz)
0
25.9
43.1
575
1.5 3
60
V
oltage (V)
Frequency (Hz)
0
25.9
43.1
575
1.5 3
60
50
V
oltage (V)
Frequency (Hz)
0
25.9
43.1
575
1.5 3
72
60
V
oltage (V)
Frequency (Hz)
Table 4.27 Derated Torque Characteristics, Settings 4 to 7
Setting = 4
50 Hz
Setting = 5
50 Hz
Setting = 6
60 Hz
Setting = 7
60 Hz
0
23.0
575
1.3
25
50
100.6
V
oltage (V)
Frequency (Hz)
0
25.9
575
1.3
25
50
143.8
V
oltage (V)
Frequency (Hz)
0
23.0
575
1.5
30
60
100.6
V
oltage (V)
Frequency (Hz)
0
25.9
575
1.5
30
60
143.8
V
oltage (V)
Frequency (Hz)
Table 4.28 High Starting Torque, Settings 8 to B
Setting = 8
50 Hz
Setting = 9
50 Hz
Setting = A
60 Hz
Setting = B
60 Hz
0
31.6
575
1.3 2.5
50
54.6
V
oltage (V)
Frequency (Hz)
0
37.4
575
1.3 2.5
50
69.0
V
oltage (V)
Frequency (Hz)
0
31.6
575
1.5 3
60
54.6
V
oltage (V)
Frequency (Hz)
0
43.1
575
1.5 3
60
69.0
V
oltage (V)
Frequency (Hz)
Table 4.29 Rated Output Operation, Settings C to F
Setting = C
90 Hz
Setting = D
120 Hz
Setting = E
180 Hz
Setting = F
60 Hz
0
25.9
43.1
575
1.5 3
90
60
V
oltage (V)
Frequency (Hz)
0
25.9
43.1
575
1.5 3
120
60
V
oltage (V)
Frequency (Hz)
0
25.9
43.1
575
1.5 3
180
60
V
oltage (V)
Frequency (Hz)
0
25.9
43.1
575
1.5 3
60
V
oltage (V)
Frequency (Hz)
Predefined V/f Patterns for Models 5A0011 to 5A0077
Table 4.30 Rated Torque Characteristics, Settings 0 to 3
Setting = 0
50 Hz
Setting = 1
60 Hz
Setting = 2
60 Hz
Setting = 3
72 Hz
0
20.1
575
1.3 2.5
50
40.3
V
oltage (V)
Frequency (Hz)
0
20.1
40.3
575
1.5 3
60
V
oltage (V)
Frequency (Hz)
V
oltage (V)
Frequency (Hz)
0
20.1
40.3
575
1.5 3
60
50
0
20.1
40.3
230
1.5 3
72
60
V
oltage (V)
Frequency (Hz)
4.13 Advanced Drive Setup Adjustments
YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual
167
4
Start-Up Programming & Operation