B.3 C: Tuning

C parameters are used to adjust the acceleration and deceleration times, S-curves, torque compensation, and carrier frequency

selections.

u

C1: Acceleration and Deceleration Times

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

C1-01

(200)

Acceleration Time 1

Accel Time 1

Sets the time to accelerate from 0 to maximum frequency.

Default: 30.0 s

Min.: 0.1

Max.: 6000.0

125

C1-02

(201)

Deceleration Time 1

Decel Time 1

Sets the time to decelerate from maximum frequency to 0.

125

C1-03

(202)

Acceleration Time 2

Accel Time 2

Sets the time to accelerate from 0 to maximum frequency.

Default: 30.0 s

Min.: 0.1

Max.: 6000.0

125

C1-04

(203)

Deceleration Time 2

Decel Time 2

Sets the time to decelerate from maximum frequency to 0.

125

C1-09

(208)

Fast Stop Time

Fast Stop Time

Sets the time for the Fast Stop function.

Default: 10.0 s

Min.: 0.1

Max.: 6000.0

C1-11

(20A)

Accel/Decel Time

Switching Frequency

Acc/Dec SW Freq

Sets the frequency to switch between accel/decel time settings.

Setting units are determined by parameter A1-02, Control

Method Selection.

Default: 0.0 Hz

Min.: 0.0

Max.: 240.0

u

C2: S-Curve Characteristics

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

C2-01

(20B)

S-Curve Characteristic

at Accel Start

SCrv Acc @ Start

The S-curve can be controlled at the four points shown below.

Run Command

Time

Output Frequency

C2-01

0.20 s <1>

C2-02

0.20 s <1>

ON

OFF

Default:

<2>

Min.: 0.00 s

Max.: 10.00 s

163

C2-02

(20C)

S-Curve Characteristic

at Accel End

SCrv Acc @ End

Default: 0.20 s

Min.: 0.00

Max.: 10.00

163

<1> S-curve characteristics at decel start/end are fixed to 0.20 s.
<2> Default setting is determined by parameter A1-02, Control Method Selection.

u

C4: Torque Compensation

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

C4-01

(215)

Torque Compensation

Gain

Torq Comp Gain

Sets the gain for the automatic torque (voltage) boost function

and helps to produce better starting torque. Used for motor 1.

Default:

<1>

Min.: 0.00

Max.: 2.50

C4-02

(216)

Torque Compensation

Primary Delay Time 1

Torq Comp Time

Sets the torque compensation filter time.

Default:

<2>

Min.: 0 ms

Max.: 60000 ms

<1> Default setting is determined by parameter A1-02, Control Method Selection.
<2> Default setting is determined by parameters A1-02, Control Method Selection, and o2-04, Drive Model Selection.

B.3 C: Tuning

270