B4: timer function, B5: pi control – Yaskawa Z1000 AC Drive HVAC User Manual

Page 266

Advertising
background image

No.

(Addr

Hex.)

Name

LCD Display

Description

Values

Page

b3-27

(1C9)

Start Speed Search

Select

Start srch sel

0: Start from 0

1: Start Fref>Fmin

Selects a condition to activate Speed Search Selection at Start

(b3-01) or External Speed Search Command 1 or 2 from the

multi-function input.

0: Triggered when a Run command is issued. (normal).

1: Triggered when an external baseblock is released.

Default: 0

Range: 0, 1

155

b3-33

(0B3F)

Speed Search Selection

when Run Command is

Given during Uv

SpdSrch Start UV

0: Disabled

1: Enabled

Activates and deactivates Speed Search at start in accordance

with whether a Run command was issued during an

undervoltage (Uv) condition. Function is active when a

momentary power loss (L2-01 = 1 or 2), Speed Search at start

(b3-01 = 1), and coasting to a stop (b1-03 = 1) are enabled.

0: Disabled

1: Enabled

Default: 0

Range: 0, 1

<1> Default setting is determined by parameter A1-02, Control Method Selection.
<2> Default setting is dependent on parameter o2-04, Drive Model Selection.

u

b4: Timer Function

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

b4-01

(1A3)

Timer Function On-

Delay Time

Delay-ON Timer

Sets the on-delay and off-delay times for a digital timer output

(H2-=12).

The output is triggered by a digital input programmed to

H1-=18).

Default: 0.0 s

Min.: 0.0

Max.: 3000.0

b4-02

(1A4)

Timer Function Off-

Delay Time

Delay-OFF Timer

Default: 0.0 s

Min.: 0.0

Max.: 3000.0

u

b5: PI Control

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

b5-01

(1A5)

PI Function Setting

PID Mode

0: Disabled

1: Enabled D=Fdbk

3: Fref+PID D=Fdbk

0: Disabled

1: Enabled (PI output becomes output frequency reference)

3: Enabled (PI output added to frequency reference)

Default: 0

Range: 0, 1, 3

155

b5-02

(1A6)

Proportional Gain

Setting (P)

PID Gain

Sets the proportional gain of the PI controller.

Default: 2.00

Min.: 0.00

Max.: 25.00

155

b5-03

(1A7)

Integral Time Setting (I) PID I Time

Sets the integral time for the PI controller.

Default: 0.5 s

Min.: 0.0

Max.: 360.0

155

b5-04

(1A8)

Integral Limit Setting

PID I Limit

Sets the maximum output possible from the integrator as a

percentage of the maximum output frequency.

Default: 100.0%

Min.: 0.0

Max.: 100.0

155

b5-06

(1AA)

PI Output Limit

PID Limit

Sets the maximum output possible from the entire PI controller

as a percentage of the maximum output frequency.

Default: 100.0%

Min.: 0.0

Max.: 100.0

156

b5-07

(1AB)

PI Offset Adjustment

PID Offset

Applies an offset to the PI controller output. Set as a percentage

of the maximum output frequency.

Default: 0.0%

Min.: -100.0

Max.: 100.0

156

b5-08

(1AC)

PI Primary Delay Time

Constant

PID Delay Time

Sets a low pass filter time constant on the output of the PI

controller.

Default: 0.00 s

Min.: 0.00

Max.: 10.00

156

b5-09

(1AD)

PI Output Level

Selection

Output Level Sel

0: Normal Character

1: Rev Character

0: Normal output (direct acting)

1: Reverse output (reverse acting)

Default: 0

Range: 0, 1

156

B.2 b: Application

266

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual