Yaskawa Z1000 AC Drive HVAC User Manual

Page 123

Advertising
background image

Setting 3: Option Card

This setting requires entering the frequency reference via an option board plugged into connector CN5 on the drive control

board. Consult the option card manual for instructions on integrating the drive with the communication system.

Note:

If the frequency reference source is set for Option PCB (b1-01 = 3), but an option board is not installed, an oPE05 Programming Error will

be displayed on the HOA keypad and the drive will not run.

n

b1-02: Run Command Selection for AUTO Mode

Determines the Run command selection for AUTO mode.

No.

Parameter Name

Setting Range

Default

b1-02

Run Command Selection for AUTO Mode

1 to 3

1

Setting 1: Control Circuit Terminal

This setting requires entering the Run command via the digital input terminals using one of following sequences:
• 2-Wire sequence 1:

Two inputs (FWD/Stop-REV/Stop). Set A1-03 to 2220 to initialize the drive and preset terminals S1 and S2 to these

functions. This is the default setting of the drive.

• 2-Wire sequence 2:

Two inputs (Start/Stop-FWD/REV).

• 3-Wire sequence:

Three inputs (Start-Stop-FWD/REV). Set A1-03 to 3330 to initialize the drive and preset terminals S1, S2, and S5 to these

functions.

Setting 2: Serial Communication (APOGEE FLN, BACnet, MEMOBUS/Modbus, Metasys N2)

This setting requires entering the Run command via serial communications by connecting the RS-422/RS-485 serial

communication cable to control terminals R+, R-, S+, and S- on the terminal block.

Setting 3: Option Card

This setting requires entering the Run command via the communication option board by plugging a communication option

board into the CN5 port on the control PCB. Refer to the option card manual for instructions on integrating the drive into the

communication system.

Note:

If b1-02 is set to 3, but an option card is not installed in CN5, an oPE05 Programming Error will be displayed on the HOA keypad and the

drive will not run.

n

b1-03: Stopping Method Selection

Selects how the drive stops the motor when the Run command is removed or when a Stop command is entered.

No.

Parameter Name

Setting Range

Default

b1-03

Stopping Method Selection

0 to 3

1

Setting 0: Ramp to Stop

When the Run command is removed, the drive will decelerate the motor to stop. The deceleration rate is determined by the

active deceleration time. The default deceleration time is set to parameter C1-02.
When the output frequency falls below the level set in parameter b2-01, the drive will start DC injection or Short Circuit

Braking depending on the selected control mode.

Refer to b2-01: DC Injection Braking Start Frequency on page 151

for

details.

Setting 1: Coast to Stop

When the Run command is removed, the drive will shut off its output and the motor will coast (uncontrolled deceleration) to

stop. The stopping time is determined by the inertia and the friction in the driven system.

4.7 Basic Drive Setup Adjustments

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual

123