H2 Multi-Function Digital Output Settings

H2-

Setting

Function

LCD Display

Description

Page

20

Drive overheat pre-

alarm (oH)

OH Prealarm

Closed: Heatsink temperature exceeds the parameter L8-02 value.

2F

Maintenance period

Maintenance

Closed: Cooling fan, electrolytic capacitors, IGBTs, or the soft charge bypass relay

may require maintenance.

37

During frequency output During RUN 2

Open: Either the drive has stopped or baseblock, DC Injection Braking, or Initial

Excitation is being performed.

Closed: Drive is running the motor (not in a baseblock state and DC Injection is

not being performed).

38

Drive enabled

Drive Enable

Closed: Multi-function input set for “Drive enable” is closed (H1- = 6A)

39

Watt hour pulse output Watt-hour Pulse

Output units are determined by H2-06. Outputs a pulse every 200 ms to indicate

the kWh count.

3A

Drive overheat alarm

OH Alarm 2

Closed: An external device triggered an overheat warning in the drive.

3D

During speed search

During SpdSrch

Closed: Speed Search is being executed.

3E

PI feedback low

PID Feedback Low

Closed: PI feedback level is too low.

3F

PI feedback high

PID FeedbackHigh

Closed: The PI feedback level is too high.

4A

During KEB Ride-Thru During KEB

Closed: KEB Ride-Thru is being performed.

4B

During short circuit

braking

During SC Brake

OLV/PM

OLV/PM

Closed: Short Circuit Braking is active.

4C

During fast stop

During Fast Stop

Closed: A Fast Stop command has been entered from the operator or input

terminals.

4D

oH Pre-alarm time limit OH Pre-Alarm

Closed: oH pre-alarm time limit has passed.

50

Waiting for run

Waiting for Run

Closed: Delay executing any run command until the time set to b1-11 has expired.

51

Sequence timer 1 active SeqTimer Disable

Closed: Sequence timer 1 is active.

52

Sequence timer 2 active SeqTimer Cancel

Closed: Sequence timer 2 is active.

53

Sequence timer 3 active Sequence timer 3

Closed: Sequence timer 3 is active.

54

Sequence timer 4 active Sequence Timer 4

Closed: Sequence timer 4 is active.

58

Underload detection

UL6

Closed: Underload is detected.

60

Internal cooling fan

alarm

Fan Alrm Det

Closed: Internal cooling fan alarm

71

Secondary PI Feedback

Low

PI2 Feedback Low

Closed: PI2 feedback level is too low.

72

Secondary PI Feedback

High

PI2 FeedbackHigh

Closed: The PI2 feedback level is too high.

A4

BP Drive Relay Contact BP Emg Override

Closed: Line voltage is being supplied to the drive, and the motor is being run via

the drive.

A5

BP Bypass Relay

Contact

BP Drv/Bypss Sel

Closed: Line voltage is being supplied directly to the motor.

A6

BP BAS Interlock Relay

Contact

BP BAS Interlock

Closed: Actuation signal for options dampers.

A9

Relay Operator Control PI2 Disable N.C.

Closed: F1 (F2) key toggle relay output.

B2

BAS Interlock Relay

Contact

BAS Interlock

A Run command is active or voltage is output. Actuation signal for damper.

100 to

1B2

Function 0 to b2 with

inverse output

Note: A prefix of "!" is

added to represent

inverse functions on the

LCD keypad display.

Example: “!Zero speed”

Inverts the output switching of the multi-function output functions.

Set the last two digits of 1 to reverse the output signal of that specific function.

B.7 H Parameters: Multi-Function Terminals

286