D.3 ul and csa standards – Yaskawa Z1000 AC Drive HVAC User Manual
Page 346
Drive Model
Terminal
Recomm. Gauge
mm
2
(AWG, kcmil)
Wire Range
mm
2
(AWG, kcmil)
Screw
Size
Tightening Torque
N·m (lb.in.)
5A0052
R/L1, S/L2, T/L3
25
(4)
6.0 to 25
(10 to 3)
M8
9.0 to 11
(79.7 to 97.4)
U/T1, V/T2, W/T3
16
(6)
6.0 to 25
(10 to 3)
⊖, ⊕1
–
16 to 35
(6 to 1)
B1, B2
–
10 to 25
(8 to 3)
16
(6)
10 to 16
(6)
5A0062
R/L1, S/L2, T/L3
25
(4)
6.0 to 95
(10 to 4/0)
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3
25
(4)
6.0 to 95
(10 to 4/0)
⊖, ⊕1
–
25 to 95
(4 to 4/0)
⊕3
–
16 to 95
(6 to 4/0)
25
(4)
25
(4)
5A0077
R/L1, S/L2, T/L3
25
(3)
6.0 to 95
(10 to 4/0)
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3
25
(3)
6.0 to 95
(10 to 4/0)
⊖, ⊕1
–
25 to 95
(3 to 4/0)
⊕3
–
16 to 95
(6 to 4/0)
25
(4)
25
(4)
5A0099
R/L1, S/L2, T/L3
70
(1/0)
6.0 to 95
(10 to 4/0)
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3
50
(1)
6.0 to 95
(10 to 4/0)
⊖, ⊕1
–
35 to 95
(2 to 4/0)
⊕3
–
25 to 95
(4 to 4/0)
25
(4)
25
(4)
5A0125
R/L1, S/L2, T/L3
70
(2/0)
35 to 150
(1 to 300)
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3
70
(2/0)
35 to 150
(1 to 300)
⊖, ⊕1
–
70
(2/0 to 3/0)
⊕3
–
35 to 50
(1 to 1/0)
35
(3)
35 to 150
(3 to 300)
5A0145
R/L1, S/L2, T/L3
95
(3/0)
95 to 150
(2/0 to 300)
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3
95
(3/0)
95 to 150
(2/0 to 300)
⊖, ⊕1
–
70 to 95
(3/0 to 4/0)
⊕3
–
70 to 95
(1/0 to 2/0)
35
(3)
35 to 150
(3 to 300)
D.3 UL and CSA Standards
346