3.10 Control I/O Connections

u

Sinking/Sourcing Mode for Digital Inputs

Use the wire jumper between terminals SC and SP or SC and SN to select between Sink mode, Source mode or external power

supply for the digital inputs S1 to S7 as shown in

Table 3.9

(Default: Sink mode, internal power supply).

NOTICE: Do not short terminals SP and SN. Failure to comply will damage the drive.

Table 3.9 Digital Input Sink/Source/External Power Supply Selection

Mode

Drive Internal Power Supply

(Terminals SN and SP)

External 24 Vdc Power Supply

Sinking Mode (NPN)

SC

S8

S7

24 Vdc

SP

SN

SC

S8

S7

24 Vdc

SP

SN

External

24 Vdc

Sourcing Mode (PNP)

SC

S8

S7

24 Vdc

SP

SN

SC

S8

S7

24 Vdc

SP

SN

External

24 Vdc

3.10 Control I/O Connections

92

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual