A.2 drive specifications – Yaskawa Z1000 AC Drive HVAC User Manual

Page 254

Advertising
background image

Item

Specification

Protection

Functions

Motor Protection

Electronic thermal overload relay

Momentary Overcurrent

Protection

Drive stops when rated output current exceeds 175%

Overload Protection

Drive stops after 60 s at 110% of rated output current

<2>

Drive stops after 0.5 s at 140% of rated output current

<2>

Overvoltage Protection

600 V class: Stops when DC bus voltage exceeds approx. 1040 V

Undervoltage Protection 600 V class: Stops when DC bus voltage falls below approx. 475 V

Momentary Power Loss

Ride-Thru

Immediately stop after 15 ms or longer power loss

<3>

Continuous operation during power loss shorter than 2 s by speed search function

Heatsink Overheat

Protection

Thermistor

Stall Prevention

Stall Prevention is available during acceleration, deceleration, and during run.

Ground Protection

Electronic circuit protection

<4>

DC Bus Charge LED

Remains lit until DC bus voltage falls below 50 V

Environment

Area of Use

Indoors

Ambient Temperature

-10 °C to +40 °C (14 to 104 °F) IP20/NEMA Type 1 Enclosure

-10 °C to +50 °C (14 to 122 °F) IP00/Open Type Enclosure

Humidity

95% RH or less (no condensation)

Storage Temperature

-20 °C to +70 °C (-4 to +158 °F) (short-term temperature during transportation)

Altitude

Up to 1000 meters without derating, up to 3000 m with output current and voltage derating.

Refer to

Altitude Derating on page 260

for details.

Vibration/Shock

10 to 20 Hz: 9.8 m/s

2

20 to 55 Hz: 5.9 m/s

2

(5A0003 to 5A0099)

2.0 m/s

2

(5A0125 to 5A0242)

Standards

• UL508C
• IEC/EN 61800-5-1
• CSA

Protection Design

IP00/Open Type enclosure, IP20/NEMA Type 1 enclosure

<5>

<1> The accuracy of these values depends on motor characteristics, ambient conditions, and drive settings. Specifications may vary with different motors

and with changing motor temperature. Contact Yaskawa for consultation.

<2> Overload protection may be triggered when operating with 150% of the rated output current if the output frequency is less than 6 Hz.
<3> May be shorter due to load conditions and motor speed.
<4> Ground protection cannot be provided when the impedance of the ground fault path is too low, or when the drive is powered up while a ground

fault is present at the output.

<5> Removing the top protective cover or bottom conduit bracket from an IP20/NEMA Type 1 enclosure drive voids NEMA Type 1 protection while

maintaining IP20 conformity. This is applicable to models 5A0003 to 5A0242.

A.2 Drive Specifications

254

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual