Yaskawa Z1000 AC Drive HVAC User Manual

Page 212

Advertising
background image

Programming error on the master side.

Check communications at start-up and correct programming errors.

Communications circuitry is damaged.

• Perform a self-diagnostics check.
• If the problem continues, replace either the control board or the entire drive. For instructions on replacing

the control board, contact Yaskawa or your nearest sales representative.

Termination resistor setting is incorrect.

Install a termination resistor at both ends of a communication line. Set the internal termination resistor switch

correctly on slave drives. Place DIP switch S2 to the ON position.

Digital Operator Display

Minor Fault Name

CE

MEMOBUS/Modbus Communication Error
Control data was not received correctly for two seconds.

Cause

Possible Solutions

A data error occurred due to noise.

• Check options available to minimize the effects of noise.
• Take steps to counteract noise in the control circuit wiring, main circuit lines, and ground wiring.
• Reduce noise on the controller side.
• Use surge absorbers for the magnetic contactors or other components that may be causing the disturbance.
• Use only recommended shielded line. Ground the shield on the controller side or on the drive input power

side.

• Separate all wiring for communication devices from drive input power lines. Install an EMC noise filter

to the drive input power supply.

Communication protocol is incompatible.

• Check the H5 parameter settings and the protocol setting in the controller.
• Ensure settings are compatible.

The CE detection time (H5-09) is set

shorter than the time required for a

communication cycle to take place.

• Check the PLC.
• Change the software settings in the PLC.
• Set a longer CE detection time using parameter H5-09.

Incompatible PLC software settings or

there is a hardware problem.

• Check the PLC.
• Remove the cause of the error on the controller side.

Communications cable is disconnected or

damaged.

• Check the connector to make sure the cable has a signal.
• Replace the communications cable.

Digital Operator Display

Minor Fault Name

CrST

Cannot Reset

Cause

Possible Solutions

Fault reset was being executed when a Run

command was entered.

• Ensure that a Run command cannot be entered from the external terminals or option during fault reset.
• Turn off the Run command.

Digital Operator Display

Minor Fault Name

dnE

Drive Disabled

Cause

Possible Solutions

“Drive Enable” is set to a multi-function

contact input (H1- = 6A) and that

signal was switched off.

Check the operation sequence.

Digital Operator Display

Minor Fault Name

EF

Forward/Reverse Run Command Input Error
Both forward run and reverse run closed simultaneously for longer than 0.5 s.

Cause

Possible Solutions

Sequence error

Check the forward and reverse command sequence and correct the problem.

Note:

When minor fault EF detected, motor ramps to stop.

Digital Operator Display

Minor Fault Name

EF0

Option Card External Fault
An external fault condition is present.

Cause

Possible Solutions

An external fault was received from the

PLC with F6-03 set to 3, which allows the

drive to continue running after an external

fault occurs.

• Remove the cause of the external fault.
• Remove the external fault input from the PLC.

There is a problem with the PLC program. Check the PLC program and correct problems.

5.5 Alarm Detection

212

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual

Advertising