Programming error on the master side.
Check communications at start-up and correct programming errors.
Communications circuitry is damaged.
• Perform a self-diagnostics check.
• If the problem continues, replace either the control board or the entire drive. For instructions on replacing
the control board, contact Yaskawa or your nearest sales representative.
Termination resistor setting is incorrect.
Install a termination resistor at both ends of a communication line. Set the internal termination resistor switch
correctly on slave drives. Place DIP switch S2 to the ON position.
Digital Operator Display
Minor Fault Name
CE
MEMOBUS/Modbus Communication Error
Control data was not received correctly for two seconds.
Cause
Possible Solutions
A data error occurred due to noise.
• Check options available to minimize the effects of noise.
• Take steps to counteract noise in the control circuit wiring, main circuit lines, and ground wiring.
• Reduce noise on the controller side.
• Use surge absorbers for the magnetic contactors or other components that may be causing the disturbance.
• Use only recommended shielded line. Ground the shield on the controller side or on the drive input power
side.
• Separate all wiring for communication devices from drive input power lines. Install an EMC noise filter
to the drive input power supply.
Communication protocol is incompatible.
• Check the H5 parameter settings and the protocol setting in the controller.
• Ensure settings are compatible.
The CE detection time (H5-09) is set
shorter than the time required for a
communication cycle to take place.
• Check the PLC.
• Change the software settings in the PLC.
• Set a longer CE detection time using parameter H5-09.
Incompatible PLC software settings or
there is a hardware problem.
• Check the PLC.
• Remove the cause of the error on the controller side.
Communications cable is disconnected or
damaged.
• Check the connector to make sure the cable has a signal.
• Replace the communications cable.
Digital Operator Display
Minor Fault Name
CrST
Cannot Reset
Cause
Possible Solutions
Fault reset was being executed when a Run
command was entered.
• Ensure that a Run command cannot be entered from the external terminals or option during fault reset.
• Turn off the Run command.
Digital Operator Display
Minor Fault Name
dnE
Drive Disabled
Cause
Possible Solutions
“Drive Enable” is set to a multi-function
contact input (H1- = 6A) and that
signal was switched off.
Check the operation sequence.
Digital Operator Display
Minor Fault Name
EF
Forward/Reverse Run Command Input Error
Both forward run and reverse run closed simultaneously for longer than 0.5 s.
Cause
Possible Solutions
Sequence error
Check the forward and reverse command sequence and correct the problem.
Note:
When minor fault EF detected, motor ramps to stop.
Digital Operator Display
Minor Fault Name
EF0
Option Card External Fault
An external fault condition is present.
Cause
Possible Solutions
An external fault was received from the
PLC with F6-03 set to 3, which allows the
drive to continue running after an external
fault occurs.
• Remove the cause of the external fault.
• Remove the external fault input from the PLC.
There is a problem with the PLC program. Check the PLC program and correct problems.