A.1 Power Ratings

u

Three-Phase 600 V Class Drive Models 5A0003 to 5A0032

Table A.1 Power Ratings (Three-Phase 600 V Class)

Item

Specification

Drive Models

5A0003

5A0004

5A0006

5A0009

5A0011

5A0017

5A0022

5A0027

5A0032

Maximum Applicable Motor Capacity

(HP)

<1>

2

3

5

7.5

10

15

20

25

30

Input

Input Current (A)

<2>

3.6

5.1

8.3

12

16

23

31

38

45

Rated Voltage

Rated Frequency

Three-phase 500 to 600 Vac 50/60 Hz

Allowable Voltage

Fluctuation

-10 (-15) to +10%

Allowable Frequency

Fluctuation

±5%

Input Power (kVA)

4.1

5.8

9.5

14

18

26

35

43

51

Output

Rated Output Capacity

(kVA)

<3> <4>

2.7

3.9

6.1

9

11

17

22

27

32

Rated Output Current

(A)

<4>

2.7

3.9

6.1

9

11

17

22

27

32

Overload Tolerance

110% of rated output for 60 s

140% of rated output for 0.5 s

Carrier Frequency

User adjustable between 1 and 12.5 kHz

Maximum Output

Voltage (V)

Three-phase 500 to 600 Vac (proportional to input voltage)

Maximum Output

Frequency (Hz)

240 Hz

<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than

the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.

<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring

connections, and power supply impedance.

<3> Rated motor capacity is calculated with a rated output voltage of 575 V.
<4> Carrier frequency is set to 2 kHz. Current derating is required to raise the carrier frequency.

A.1 Power Ratings

250