Power ratings, A.1 power ratings – Yaskawa Z1000 AC Drive HVAC User Manual
Page 250
A.1 Power Ratings
u
Three-Phase 600 V Class Drive Models 5A0003 to 5A0032
Table A.1 Power Ratings (Three-Phase 600 V Class)
Item
Specification
Drive Models
5A0003
5A0004
5A0006
5A0009
5A0011
5A0017
5A0022
5A0027
5A0032
Maximum Applicable Motor Capacity
(HP)
<1>
2
3
5
7.5
10
15
20
25
30
Input
Input Current (A)
<2>
3.6
5.1
8.3
12
16
23
31
38
45
Rated Voltage
Rated Frequency
Three-phase 500 to 600 Vac 50/60 Hz
Allowable Voltage
Fluctuation
-10 (-15) to +10%
Allowable Frequency
Fluctuation
±5%
Input Power (kVA)
4.1
5.8
9.5
14
18
26
35
43
51
Output
Rated Output Capacity
(kVA)
<3> <4>
2.7
3.9
6.1
9
11
17
22
27
32
Rated Output Current
(A)
<4>
2.7
3.9
6.1
9
11
17
22
27
32
Overload Tolerance
110% of rated output for 60 s
140% of rated output for 0.5 s
Carrier Frequency
User adjustable between 1 and 12.5 kHz
Maximum Output
Voltage (V)
Three-phase 500 to 600 Vac (proportional to input voltage)
Maximum Output
Frequency (Hz)
240 Hz
<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than
the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
connections, and power supply impedance.
<3> Rated motor capacity is calculated with a rated output voltage of 575 V.
<4> Carrier frequency is set to 2 kHz. Current derating is required to raise the carrier frequency.
A.1 Power Ratings
250