Main circuit wiring, Main circuit terminal functions, Protecting main circuit terminals – Yaskawa Z1000 AC Drive HVAC User Manual

Page 80: 8 main circuit wiring

Advertising
background image

3.8 Main Circuit Wiring

This section describes the functions, specifications, and procedures required to safely and properly wire the main circuit in

the drive.

NOTICE: Do not solder the ends of wire connections to the drive. Soldered wiring connections can loosen over time. Improper wiring practices

could result in drive malfunction due to loose terminal connections.

NOTICE: Do not switch the drive input to start or stop the motor. Frequently switching the drive on and off shortens the life of the DC bus

charge circuit and the DC bus capacitors, and can cause premature drive failures. For the full performance life, refrain from switching the

drive on and off more than once every 30 minutes.

Refer to Factory Recommended Branch Circuit Protection for UL Compliance on page 247

for details on fuse selection.

u

Main Circuit Terminal Functions

Table 3.1 Main Circuit Terminal Functions

Terminal

Type

Function

Page

Drive Model

5A0003 to 5A0032

5A0041, 5A0052

5A0062 to 5A0242

R/L1

Main circuit power supply input

Connects line power to the drive

71

S/L2

T/L3
U/T1

Drive output

Connects to the motor

71

V/T2

W/T3

B1

Braking resistor

Not available

Available for connecting a braking

resistor or a braking resistor unit option

B2

2

• DC link choke

connection

(

⊕1, ⊕2)

(remove the shorting

bar between

⊕1 and ⊕2)

• DC power supply

input

(

⊕1, ⊖)

Not available

For connecting:
• the drive to a DC power supply
• dynamic braking options
• a DC link choke

1

DC power supply input

(

⊕1, ⊖)

• DC power supply

input (

⊕1, ⊖)

• Braking unit

connection (

⊕3, ⊖)

3

Not available

10 Ω or less

Grounding terminal

84

Note:

Use terminals B1 and

⊖ when installing a CDBR-type braking unit on drives with built-in braking transistors (Models 5A0003 to 5A0052).

u

Protecting Main Circuit Terminals

n

Insulation Caps or Sleeves

Use insulation caps or sleeves when wiring the drive with crimp terminals. Take particular care to ensure that the wiring does

not touch nearby terminals or the surrounding case.

3.8 Main Circuit Wiring

80

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual

Advertising