Auto-tuning interruption and fault codes, Auto-tuning operation example, Selecting the type of auto-tuning – Yaskawa Z1000 AC Drive HVAC User Manual

Page 138: 8 auto-tuning, Stationary auto-tuning for line-to-line resistance, Press or until the auto-tuning display appears, Press to begin setting parameters, Press to display the value for t1-01, Save the setting by pressing

Advertising
background image

WARNING! Electrical Shock Hazard. When executing stationary Auto-Tuning, voltage is applied to the motor before the motor rotates. Do

not touch the motor until Auto-Tuning is completed. Failure to comply may result in injury or death from electrical shock.

WARNING! Sudden Movement Hazard. If installed, do not release the mechanical brake during Stationary Auto-Tuning. Inadvertent brake

release may cause damage to equipment or injury to personnel. Ensure that the mechanical brake release circuit is not controlled by the

drive multi-function digital outputs.

Stationary Auto-Tuning for Line-to-Line Resistance

• Perform when entering motor data manually while using motor cables longer than 50 m.
• If the motor cables have been replaced with cables more than 50 m long after Auto-Tuning has already been performed, use

Stationary Auto-Tuning for line-to-line resistance.

u

Auto-Tuning Interruption and Fault Codes

If tuning results are abnormal or the OFF key is pressed before completion, Auto-Tuning will be interrupted and a fault code

will appear on the HOA keypad.

B

LO

RE

ESC

RUN

STOP

ENTER

RESET

DIGITAL OPERATOR JVOP-180

A

LO

RE

ESC

RUN

STOP

ENTER

RESET

DIGITAL OPERATOR JVOP-180

ALM

ALM

- A.TUNE -

X.XX Hz/ X.XXA

DRV

Tune Proceeding

Rdy

FWD

<

<<

<<< >>>

>>

>

- MODE -

Er-03

STOP key

DRV

FWD

RESET

A – During Auto-Tuning

B – Auto-Tuning Aborted

Figure 4.27 Auto-Tuning Aborted Display

u

Auto-Tuning Operation Example

The following example demonstrates Rotational Auto-Tuning for V/f.

n

Selecting the Type of Auto-Tuning

Step

Display/Result

1. Turn on the power to the drive. The initial display appears.

- MODE -

U1-01= 0.00Hz
U1-02= 0.00Hz

U1-03= 0.00 A

DRV

Freq Ref (AI)

Rdy

FWD

LSEQ

LREF

2. Press

or

until the Auto-Tuning display appears.

HELP

- MODE -

PRG

Auto-Tuning

DATA

AUTO

FWD

3. Press

to begin setting parameters.

- A.TUNE -

T1-

01

= 2

*2*

Line-to-Line

PRG

Tuning Mode Sel

Rdy

ESC

FWD

DATA

4. Press

to display the value for T1-01.

- A.TUNE -

T1-01=

2

*2*

Line-to-Line

PRG

Tuning Mode Sel

Rdy

FWD

“0”

5. Save the setting by pressing

.

Entry Accepted

6. The display automatically returns to the display shown in Step 3.

- A.TUNE -

T1-

01

= 3

*3*

V/f Engy Sav Tun

PRG

Tuning Mode Sel

Rdy

ESC

FWD

DATA

4.8 Auto-Tuning

138

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual

Advertising