4.9 No-Load Operation Test Run

u

No-Load Operation Test Run

This section explains how to operate the drive with the motor decoupled from the load during a test run.

n

Before Starting the Motor

Check the following items before operation:
• Ensure the area around the motor is safe.
• Ensure external emergency stop circuitry is working properly and other safety precautions have been taken.

n

During Operation

Check the following items during operation:
• The motor should rotate smoothly (i.e., no abnormal noise or oscillation).
• The motor should accelerate and decelerate smoothly.

n

No-Load Operation Instructions

The following example illustrates a test run procedure using the HOA keypad.

Step

Display/Result

1. Before starting the motor, set parameter d1-01, Frequency Reference, to 6 Hz.

The Run command from AUTO mode must be OFF.

2. Turn on the power to the drive. The initial display appears.

- MODE -

U1-01= 0.00Hz
U1-02= 0.00Hz

U1-03= 0.00 A

DRV

Freq Ref (AI)

Rdy

FWD

LSEQ

LREF

3. Press

HAND

to give the drive a Run command from HAND mode. The HAND light will

turn on and the motor will rotate at 6 Hz.

F2

F1

ESC

M

M

AUTO

OFF

ENTER

RESET

-DRIVE-

U1- 01=60.00Hz

----------------

U1- 02=60.00Hz

JOG FWD FWD/REV

-Rdy-

ALM

DIGITAL OPERATOR JVOP-183

HAND

ENTER

Off

On

- MODE -

U1-01= 0.00Hz
U1-02= 0.00Hz

U1-03= 0.00 A

DRV

Freq Ref (OPR)

Rdy

JOG

FWD

FWD/REV

LSEQ

LREF

HAND

HAND

4. Ensure the motor is rotating in the correct direction and that no faults or alarms occur.

Motor

Forward

5.

If there is no error in step 3, press

to increase the frequency reference. Increase the

frequency in increments of 10 Hz, verifying smooth operation at all speeds. For each

frequency, check the drive output current using monitor U1-03. The current should be well

below the motor rated current.

6. The drive should operate normally. Press

OFF

to stop the motor. The HAND light is

OFF and the motor coasts to stop.

F2

F1

ESC

M

M

AUTO

OFF

ENTER

RESET

-DRIVE-

U1- 01=60.00Hz

----------------

U1- 02=60.00Hz

JOG FWD FWD/REV

-Rdy-

ALM

DIGITAL OPERATOR JVOP-183

HAND

On

Off

- MODE -

U1-01= 0.00Hz
U1-02= 0.00Hz

U1-03= 0.00 A

DRV

FREF (OPR)

Rdy

JOG

FWD

FWD/REV

LSEQ

LREF

HAND

HAND

- MODE -

U1-01= 60.00Hz
U1-02= 0.00Hz

U1-03= 0.00A

DRV

Freq Ref (OPR)

Rdy

JOG

FWD

FWD/REV

LSEQ

LREF

4.9 No-Load Operation Test Run

144