No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

b5-26

(1E8)

PI Maximum Boost

Time

SetpointBoostTim

Sets the maximum boost time when PI feedback does not reach

boost level.

The Snooze Function starts when the PI feedback exceeds the

boost setting level or when the boost time expires.

Default: 0s

Min.: 0

Max.: 2600

159

b5-27

(1E9)

PI Snooze Feedback

Level

Snooze Reset Lvl

Sets the PI feedback level above which Snooze mode is

activated. Set as a percentage of the maximum frequency.

Default: 60%

Min.: 0

Max.: 100

159

b5-28

(1EA)

PI Feedback Function

Selection

PI Fdbk Sqrt Sel

0: Disabled

1: Enabled

0: Disabled

1: Square root

Default: 0

Range: 0, 1

160

b5-29

(1EB)

PI Square Root Gain

PI Fdbk SqrtGain

A multiplier applied to the square root of the feedback.

Default: 0.00

Min.: 0.00

Max.: 2.00

160

b5-30

(1EC)

PI Feedback Offset

PI Fdbk Offset

PI feedback offset set as a percentage of the maximum

frequency.

Default: 0.00

Min.: 0.00

Max.: 100.00

160

b5-34

(19F)

PI Output Lower Limit PID Out Low Lim

Sets the minimum output possible from the PI controller as a

percentage of the maximum output frequency.

Default: 0.0%

Min.: -100.0

Max.: 100.0

160

b5-35

(1A0)

PI Input Limit

PID Input Limit

Limits the PI control input (deviation signal) as a percentage of

the maximum output frequency. Acts as a bipolar limit.

Default:

1000.0%

Min.: 0.0

Max.: 1000.0

160

b5-36

(1A1)

PI Feedback High

Detection Level

Fb High Det Lvl

Sets the PI feedback high detection level as a percentage of the

maximum output frequency.

Default: 100%

Min.: 0

Max.: 100

160

b5-37

(1A2)

PI Feedback High

Detection Time

Fb High Dly Time

Sets the PI feedback high level detection delay time.

Default: 1.0 s

Min.: 0.0

Max.: 25.5

160

b5-38

(1FE)

PI Setpoint User Display PID UsrDspMaxVal

Sets the display value of U5-01 and U5-04 when the maximum

frequency is output.

Default:

<3>

Min.: 1

Max.: 60000

161

b5-39

(1FF)

PI Setpoint Display

Digits

PID UsrDspDigits

0: No Dec (XXXXX)

1: 1 Dec (XXXX.X)

2: 2 Dec (XXX.XX)

3: 3 Dec (XX.XXX)

0: No decimal places

1: One decimal place

2: Two decimal places

3: Three decimal places

Default:

<3>

Range: 0 to 3

161

b5-40

(17F)

Frequency Reference

Monitor Content during

PI

Fref Mon Sel@PID

0: Fref Mon w PID

1: Fref Mon w/o PID

0: Display the frequency reference (U1-01) after PI

compensation has been added.

1: Display the frequency reference (U1-01) before PI

compensation has been added.

Default: 0

Range: 0, 1

161

b5-41

(160)

PI Unit Selection

PI Mon Unit Sel

0: WC

1: PSI

2: GPM

3: °F

4: CFM

5: CMH

6: LPH

7: LPS

8: Bar

9: Pa

10: °C

11: Mtr

12: Ft

13: LPM

14: CMM

0: WC (Inch of water)

1: PSI (Pounds per square inch)

2: GPM (Gallons per minute)

3: F (Degrees Fahrenheit)

4: CFM (Cubic feet per minute)

5: CMH (Cubic meters per hour)

6: LPH (Liters per hour)

7: LPS (Liters per second)

8: Bar (Bar)

9: Pa (Pascal)

10: C (Degrees Celsius)

11: Mtr (Meters)

12: Ft (Feet)

13: LPM (Liters per minute)

14: CMM (Cubic meters per minute)

Default: 0

Range: 0 to 14

161

b5-42

(161)

PI Output Monitor

Calculation Method

PI Out Calc Mode

0: Linear

1: Square root

2: 1/f2

3: 1/f3

0: Linear - the monitor displays PI output

1: Square root - the monitor displays square root PI output

2: Quadratic - the monitor displays 1/(PI output)

3: Cubic - the monitor displays 1/(PI output)

Default: 0

Range: 0 to 3

161

B.2 b: Application

268