Yaskawa Z1000 AC Drive HVAC User Manual

Page 122

Advertising
background image

Drive

A1 Analog Input 1

0 to 10 V

AC Analog input common

2 k

+V 10.5 V, 20 mA power supply

A2 Analog Input 2

V

I

A1 A2

Jumper S1
Terminal A1/A2
Voltage/Current
Selection

V

I

A1 A2

Figure 4.12 Setting the Frequency Reference as a Voltage Signal at Terminal A1

Use the wiring example shown in

Figure 4.12

for any other analog input terminals. When using input terminals A1 and A2,

make sure Jumper S1 is set for voltage input.
Current Input
Input terminals A1 and A2 can accept a current input signal. Refer to

Table 4.16

to set terminals A1 and A2 for current input.

Table 4.16 Analog Input Settings for Frequency Reference Using a Current Signal

Terminal

Signal

Level

Parameter Settings

Notes

Signal Level

Selection

Function

Selection

Gain

Bias

A1

4 to 20 mA

H3-01 = 2

H3-02 = 0

(Frequency

Reference Bias)

H3-03

H3-04

Make sure to set Jumper S1 on the

terminal board to “I” for current

input.

0 to 20 mA

H3-01 = 3

A2

4 to 20 mA

H3-09 = 2

H3-10 = 0

(Frequency Bias)

H3-11

H3-12

0 to 20 mA

H3-09 = 3

Drive

A1 Analog Input 1

0 or 4 to 20 mA

AC Analog input common

+V 10.5 V, 20 mA power supply

A2 Analog Input 2

V

I

A1 A2

Jumper S1
Terminal A1/A2
Voltage/Current
Selection

V

I

A1 A2

Figure 4.13 Setting the Frequency Reference as a Current Signal to Terminal A2

Switching between Main/Auxiliary Frequency References

The frequency reference input can be switched between the analog terminals A1 and A2 using multi-speed inputs.

Refer to

Multi-Step Speed Selection on page 164

for details on using this function.

Setting 2: Serial Communication (APOGEE FLN, BACnet, MEMOBUS/Modbus, Metasys N2)

This setting requires entering the frequency reference via the RS-422/RS-485 serial communications port (control terminals

R+, R-, S+, and S-).

4.7 Basic Drive Setup Adjustments

122

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual

Advertising