o3: Copy Function

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

o3-01

(515)

Copy Function Selection

COPY SELECT

0: COPY SELECT

1: INV→OP READ

2: OP→INV WRITE

3: OP←→INV

VERIFY

0: No action

1: Read parameters from the drive, saving them onto the HOA

keypad.

2: Copy parameters from the HOA keypad, writing them to the

drive.

3: Verify parameter settings on the drive to check if they match

the data saved on the HOA keypad.

Default: 0

Range: 0 to 3

184

o3-02

(516)

Copy Allowed Selection

Read Allowable

0: Disabled

1: Enabled

0: Read operation prohibited

1: Read operation allowed

Default: 0

Range: 0, 1

184

u

o4: Maintenance Monitor Settings

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

o4-01

(50B)

Cumulative Operation

Time Setting

DrvElapsTimeCnt

Sets the value for the cumulative operation time of the drive in

units of 10 h.

Default: 0 h

Min.: 0

Max.: 9999

184

o4-02

(50C)

Cumulative Operation

Time Selection

ElapsTimeCntSet

0: Power-On Time

1: Running Time

0: Logs power-on time

1: Logs operation time when the drive output is active (output

operation time).

Default: 1

Range: 0, 1

184

o4-03

(50E)

Cooling Fan Operation

Time Setting

FanElapsTimeCn

Sets the value of the fan operation time monitor U4-03 in units

of 10 h.

Default: 0 h

Min.: 0

Max.: 9999

184

o4-05

(51D)

Capacitor Maintenance

Setting

BusCap Maint Set

Sets the value of the Maintenance Monitor for the capacitors. See

U4-05 to check when the capacitors may need to be replaced.

Default: 0%

Min.: 0

Max.: 150

185

o4-07

(523)

DC Bus Pre-Charge

Relay Maintenance

Setting

ChrgCircMaintSet

Sets the value of the Maintenance Monitor for the soft charge

bypass relay. See U4-06 to check when the bypass relay may need

to be replaced.

Default: 0%

Min.: 0

Max.: 150

185

o4-11

(510)

U2, U3 Initialization

Fault Data Init

0: No Reset

1: Reset

0: U2- and U3- monitor data is not reset when the drive

is initialized (A1-03).

1: U2- and U3- monitor data is reset when the drive is

initialized (A1-03).

Default: 0

Range: 0, 1

185

o4-12

(512)

kWh Monitor

Initialization

kWh Monitor Init

0: No Reset

1: Reset

0: U4-10 and U4-11 monitor data is not reset when the drive is

initialized (A1-03).

1: U4-10 and U4-11 monitor data is reset when the drive is

initialized (A1-03).

Default: 0

Range: 0, 1

185

o4-13

(528)

Number of Run

Commands Counter

Initialization

Run Counter Init

0: No Reset

1: Reset

0: Number of Run commands counter is not reset when the drive

is initialized (A1-03).

1: Number of Run commands counter is reset when the drive is

initialized (A1-03).

Default: 0

Range: 0, 1

185

o4-17

(3100)

Set/Reset Real Time

Clock

Set Time

0: — —

1: Set

2: Reset

Sets the current date and time for the Real Time Clock.

0: — — No Setting

1: Real Time Clock Set

2: Real Time Clock Reset

Default: 0

Range: 0 to 2

185