Yaskawa Z1000 AC Drive HVAC User Manual

Page 130

Advertising
background image

n

E5-07: Motor q-Axis Inductance (Lq)

Sets the q-Axis inductance in 0.01 mH units.

No.

Parameter Name

Setting Range

Default

E5-07

Motor q-Axis Inductance

0.00 to 600.00 mH

Determined by

o2-04

n

E5-09: Motor Induction Voltage Constant 1 (Ke)

Sets the induced peak voltage per phase in units of 0.1 mV/(rad/s) [electrical angle]. Set this parameter when using an IPM

motor with variable torque.

No.

Parameter Name

Setting Range

Default

E5-09

Motor Induction Voltage Constant 1

0.0 to 2000.0 mV/(rad/s)

Determined by

o2-04

Note:

Set E5-24 to 0 when setting E5-09. However, setting both E5-09 and E5-24 to 0 will trigger an alarm. An alarm will also be triggered if

neither E5-09 nor E5-24 are set to 0.

n

E5-24: Motor Induction Voltage Constant 2 (Ke)

Set the induced phase-to-phase rms voltage in units of 0.1 mV/(r/min) [mechanical angle]. Set this parameter when using an

SPM Motor.

No.

Parameter Name

Setting Range

Default

E5-24

Motor Induction Voltage Constant 2

0.0 to 6500.0 mV/(r/min)

Determined by

o2-04

Note:

Set E5-24 to 0.0 when setting E5-09. However, setting both E5-09 and E5-24 to 0.0 will trigger an alarm. An alarm will also be triggered

if neither E5-09 nor E5-24 are set to 0.0.

n

H3-03, H3-04: Terminal A1 Gain and Bias Settings

Parameter H3-03 sets the level of the selected input value that is equal to 10 Vdc (20 mA) input at terminal A1 (gain).
Parameter H3-04 sets the level of the selected input value that is equal to 0 V (4 mA, 0 mA) input at terminal A1 (bias).
Use both parameters to adjust the characteristics of the analog input signal to terminal A1.

No.

Name

Setting Range

Default

H3-03

Terminal A1 Gain Setting

-999.9 to 999.9%

100.0%

H3-04

Terminal A1 Bias Setting

-999.9 to 999.9%

0.0%

Setting Examples

• Gain H3-03 = 200%, bias H3-04 = 0, terminal A1 as frequency reference input (H3-02 = 0):

A 10 Vdc input is equivalent to a 200% frequency reference and 5 Vdc is equivalent to a 100% frequency reference. Since

the drive output is limited by the maximum frequency parameter (E1-04), the frequency reference will be equal to E1-04

above 5 Vdc.

H3-01 = 0

10 V

5 V

0 V

Gain = 200 %

100 %

Frequency
reference

Bias = 0 %

E1-04

Figure 4.23 Frequency Reference Setting by Analog Input with Increased Gain

• Gain H3-03 = 100%, bias H3-04 = -25%, terminal A1 as frequency reference input:

4.7 Basic Drive Setup Adjustments

130

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual

Advertising