5.10 Troubleshooting without Fault Display

This section describes troubleshooting problems that do not trip an alarm or fault.
The following symptoms indicate that the drive is not set correctly for proper performance with the motor.

Refer to Motor

Performance Fine-Tuning on page 192

for guidance on troubleshooting.

• Motor hunting and oscillation
• Poor motor torque
• Poor speed precision
• Poor motor torque and speed response
• Motor noise

u

Common Problems

Common Problems

Page

Cannot Change Parameter Settings

228

Motor Does Not Rotate Properly after Pressing the AUTO

Button or after Entering External Run Command

Motor Does Not Rotate

229

Motor Rotates in the Opposite Direction from the Run

Command

230

Motor Rotates in One Direction Only

230

Motor is Too Hot

230

oPE02 Error Occurs When Lowering the Motor Rated Current Setting

231

Motor Stalls During Acceleration or With Large Loads

231

Drive Frequency Reference Differs from the Controller Frequency Reference Command

232

Excessive Motor Oscillation and Erratic Rotation

232

Deceleration Takes Longer Than Expected

232

Noise From Drive or Motor Cables When the Drive is Powered On

232

Ground Fault Circuit Interrupter (GFCI) Trips During Run

232

Connected Machinery Vibrates When Motor Rotates

Unexpected Noise from Connected Machinery

233

Oscillation or Hunting

233

PI Output Fault

233

Motor Rotates After the Drive Output is Shut Off (Motor Rotates During DC Injection Braking)

233

Output Frequency is not as High as Frequency Reference

234

Sound from Motor

234

Unstable Motor Speed when Using PM

234

Motor Does Not Restart after Power Loss

234

u

Cannot Change Parameter Settings

Cause

Possible Solutions

The drive is running the motor

(i.e., the Run command is present).

• Stop the drive and switch over to the Programming Mode.
• Most parameters cannot be edited during run.

The Access Level is set to restrict access to parameter

settings.

• Set the Access Level to allow parameters to be edited (A1-01 = 2).

The operator is not in the Parameter Setup Mode

(the screen will display “PAr”).

• See what mode the operator is currently set for.
• Parameters cannot be edited when in the Setup Mode (“STUP”). Switch modes so that “PAr”

appears on the screen.

Refer to The Drive, Programming, and Clock Adjustment Modes on

page 106

.

A multi-function contact input terminal is set to allow

or restrict parameter editing

(H1-01 through H1-07 = 1B).

• When the terminal is open, parameters cannot be edited.
• Turn on the multi-function contact input set to 1B.

5.10 Troubleshooting without Fault Display

228