Main Circuit Terminal and Motor Wiring

This section outlines the various steps, precautions, and checkpoints for wiring the main circuit terminals and motor terminals.

WARNING! Electrical Shock Hazard. Do not connect the AC power line to the output terminals of the drive. Failure to comply could result

in death or serious injury by fire as a result of drive damage from line voltage application to output terminals.

NOTICE: When connecting the motor to the drive output terminals U/T1, V/T2, and W/T3, the phase order for the drive and motor should

match. Failure to comply with proper wiring practices may cause the motor to run in reverse if the phase order is backward.

NOTICE: Route motor leads U/T1, V/T2, and W/T3 separate from all other leads to reduce possible interference related issues. Failure to

comply may result in abnormal operation of drive and nearby equipment.

NOTICE: Do not connect phase-advancing capacitors or LC/RC noise filters to the output circuits. Failure to comply could result in damage

to the drive, phase-advancing capacitors, LC/RC noise filters or ground fault circuit interrupters.

n

Cable Length Between Drive and Motor

Voltage drop along the motor cable may cause reduced motor torque when the wiring between the drive and the motor is too

long, especially at low frequency output. This can also be a problem when motors are connected in parallel with a fairly long

motor cable. Drive output current will increase as the leakage current from the cable increases. An increase in leakage current

may trigger an overcurrent situation and weaken the accuracy of the current detection.
Adjust the drive carrier frequency according to

Table 3.3

. If the motor wiring distance exceeds 100 m because of the system

configuration, reduce the ground currents.

Refer to C6-02: Carrier Frequency Selection on page 126

.

Table 3.3 Cable Length Between Drive and Motor

Cable Length

50 m or less

100 m or less

Greater than 100 m

Carrier Frequency

15 kHz or less

5 kHz or less

2 kHz or less

Note:

When setting carrier frequency for drives running multiple motors, calculate cable length as the total wiring distance to all connected motors.

n

Ground Wiring

Follow the precautions below when wiring the ground for one drive or a series of drives.

WARNING! Electrical Shock Hazard. Make sure the protective earthing conductor complies with technical standards and local safety

regulations. Failure to comply may result in death or serious injury.

WARNING! Electrical Shock Hazard. Always use a ground wire that complies with technical standards on electrical equipment and minimize

the length of the ground wire. Improper equipment grounding may cause dangerous electrical potentials on equipment chassis, which could

result in death or serious injury.

WARNING! Electrical Shock Hazard. Be sure to ground the drive ground terminal (600 V class: ground to 10 Ω or less). Improper equipment

grounding could result in death or serious injury by contacting ungrounded electrical equipment.

NOTICE: Do not share the ground wire with other devices such as welding machines or large-current electrical equipment. Improper

equipment grounding could result in drive or equipment malfunction due to electrical interference.

NOTICE: When using more than one drive, ground multiple drives according to instructions. Improper equipment grounding could result in

abnormal operation of drive or equipment.

Refer to

Figure 3.18

when using multiple drives. Do not loop the ground wire.

Figure 3.18 Multiple Drive Wiring

n

Wiring the Main Circuit Terminal

WARNING! Electrical Shock Hazard. Shut off the power supply to the drive before wiring the main circuit terminals. Failure to comply may

result in death or serious injury.

Wire the main circuit terminals after the terminal board has been properly grounded.

3.8 Main Circuit Wiring