L3-05

(493)

Stall Prevention

Selection during Run

StallP Run Sel

0: Disabled

1: Decel time

2: Decel time 2

0: Disabled. Drive runs at a set frequency. A heavy load may

cause speed loss.

1: Decel time 1. Uses the deceleration time set to C1-02 while

Stall Prevention is performed.

2: Decel time 2. Uses the deceleration time set to C1-04 while

Stall Prevention is performed.

Default: 1

Range: 0 to 2

L3-06

(494)

Stall Prevention Level

during Run

StallP Run Level

Enabled when L3-05 is set to 1 or 2. 100% is equal to the drive

rated current.

Default:

<1>

Min.: 30%
Max.: 150%

<1>

L3-11

(4C7)

Overvoltage

Suppression Function

Selection

OV Inhibit Sel

0: Disabled

1: Enabled

Enables or disables the ov suppression function, which allows

the drive to change the output frequency as the load changes to

prevent an ov fault.

0: Disabled

1: Enabled

Default: 0

Range: 0, 1

L3-17

(462)

Target DC Bus Voltage

for Overvoltage

Suppression and Stall

Prevention

DC Bus Reg Level

Sets the desired value for the DC bus voltage during overvoltage

suppression and Stall Prevention during deceleration.

Default: 1063.8
Vdc

<3>

Min.: 431.3

Max.: 1150.0

L3-20

(465)

DC Bus Voltage

Adjustment Gain

DC Bus P Gain

Determines the proportional gain used by overvoltage

suppression (L3-11 = 1), Single drive KEB 2 (L2-29 = 1), KEB

Ride-Thru 2 (H1- = 7A or 7B), and Intelligent Stall

Prevention during Deceleration (L3-04 = 2) to control the DC

bus voltage in OLV/PM.

Default:

<4>

Min.: 0.00

Max.: 5.00

L3-21

(466)

Accel/Decel Rate

Calculation Gain

Acc/Dec P Gain

Sets the proportional gain used to calculate the deceleration rate

during KEB Ride-Thru, ov suppression function, and Stall

Prevention during deceleration (L3-04 = 2).

Default:

<4>

Min.: 0.00

Max.: 200.00

L3-22

(4F9)

Deceleration Time at

Stall Prevention during

Acceleration

PM Acc Stall P T

Sets the deceleration time used for Stall Prevention during

acceleration in OLV/PM.

Default: 0.0 s

Min.: 0.0

Max.: 6000

L3-23

(4FD)

Automatic Reduction

Selection for Stall

Prevention during Run

CHP Stall P Sel

0: Lv1 set in L3-06

1: Autom. Reduction

0: Sets the Stall Prevention level set in L3-04 that is used

throughout the entire frequency range.

1: Automatic Stall Prevention level reduction in the constant

output range. The lower limit value is 40% of L3-06.

Default: 0

Range: 0, 1

L3-24

(46E)

Motor Acceleration

Time for Inertia

Calculations

Mtr Accel Time

OLV/PM

OLV/PM

Sets the time needed to accelerate the uncoupled motor at rated

torque from stop to the maximum frequency.

Default:

<5> <6>

Min: 0.001 s

Max: 10.000 s

L3-25

(46F)

Load Inertia Ratio

Load Inertia Rat

OLV/PM

OLV/PM

Sets the ratio between the motor and machine inertia.

Default: 1.0

Min.: 1.0

Max.: 1000.0

L3-26

(455)

Additional DC Bus

Capacitors

ExtDC busCapSize

When DC bus capacitors have been added externally, be sure

to add those values to the internal capacitor table for proper DC

bus calculations.

Default: 0 μF

Min: 0

Max: 65000

L3-27

(456)

Stall Prevention

Detection Time

Stl Prev DetTime

Sets the time the current must exceed the Stall Prevention level

to activate Stall Prevention.

Default: 50 ms

Min.: 0

Max.: 5000

<1> Upper limit is dependent on parameter L8-38, Frequency Reduction Selection.
<2> The setting range is 0 to 2 in OLV/PM control mode.
<3> Default setting is dependent on parameter E1-01, Input voltage Setting.
<4> Default setting is determined by parameter A1-02, Control Mode Setting.
<5> Parameter value changes automatically if E2-11 is manually changed or changed by Auto-Tuning.
<6> Default setting is dependent on parameter o2-04, Drive Model Selection.

B.8 L: Protection Function

292