3.5 Terminal Cover

Follow the procedure below to remove the terminal cover for wiring and to reattach the terminal cover after wiring is complete.

u

Models 5A0003 to 5A0032 (IP20/NEMA Type 1 Enclosure)

n

Removing the Terminal Cover

1.

Loosen the terminal cover screw using a #2 Phillips screwdriver. Screw sizes vary by drive model.

Figure 3.7 Removing the Terminal Cover on an IP20/NEMA Type 1 Enclosure Drive

2.

Push in on the tab located on the bottom of the terminal cover and gently pull forward to remove the terminal cover.

Figure 3.8 Removing the Terminal Cover on an IP20/NEMA Type 1 Enclosure Drive

n

Reattaching the Terminal Cover

Power lines and signal wiring should pass through the opening provided.

Refer to Wiring the Main Circuit Terminal on

page 84

and

Wiring the Control Circuit Terminal

on page

89

for details on wiring.

Reattach the terminal cover after completing the wiring to the drive and other devices.

<1>

Figure 3.9 Reattaching the Terminal Cover on an IP20/NEMA Type 1 Enclosure Drive

<1> Connect the ground wiring first, then the main circuit wiring, and finally the control circuit wiring.

3.5 Terminal Cover

76