No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

b5-10

(1AE)

PI Output Gain Setting Output Gain

Sets the gain applied to the PI output.

Default: 1.00

Min.: 0.00

Max.: 25.00

156

b5-11

(1AF)

PI Output Reverse

Selection

Output Rev Sel

0: 0 limit

1: Reverse

0: Negative PI output triggers zero limit.

1: Rotation direction reverses with negative PI output.

Note:

When using setting 1, make sure reverse

operation is permitted by b1-04.

Default: 0

Range: 0, 1

156

b5-12

(1B0)

PI Feedback Loss

Detection Selection

Fb loss Det Sel

0: DO Only - Always

1: Alarm - Always

2: Fault - Always

3: DO Only@PID

Enbl

4: Alarm @ PID Enbl

5: Fault @ PID Enbl

0: Digital Output Only

(Remains active when PI is disabled by digital input)

1: Alarm output, drive continues operation (Remains active

when PI is disabled by digital input)

2: Fault output, drive output is shut off (Remains active when

PI is disabled by digital input)

3: Digital output only. No detection when PI is disabled by

digital input.

4: Alarm detection. No detection when PI is disabled by digital

input.

5: Fault detection. No detection when PI is disabled by digital

input.

Default: 0

Range: 0 to 5

156

b5-13

(1B1)

PI Feedback Loss

Detection Level

Fb loss Det Lvl

Sets the PI feedback loss detection level as a percentage of the

maximum output frequency.

Default: 0%

Min.: 0

Max.: 100

157

b5-14

(1B2)

PI Feedback Loss

Detection Time

Fb loss Det Time

Sets a delay time for PI feedback loss.

Default: 1.0 s

Min.: 0.0

Max.: 25.5

157

b5-15

(1B3)

PI Sleep Function Start

Level

PID Sleep Level

Sets the frequency level that triggers the sleep/snooze function. Default:

<1>

Min.: 0.0 Hz

Max.: 240.0 Hz

157

b5-16

(1B4)

PI Sleep Delay Time

PID Sleep Time

Sets a delay time before the sleep/snooze function is triggered. Default: 0.0 s

Min.: 0.0

Max.: 25.5

158

b5-17

(1B5)

PI Accel/Decel Time

PID Acc/Dec Time

Sets the acceleration and deceleration time to PI setpoint.

Default: 0.0 s

Min.: 0.0

Max.: 6000.0

158

b5-18

(1DC)

PI Setpoint Selection

PID Setpoint Sel

0: Disabled

1: Enabled

0: Disabled

1: Enabled

Default: 0

Range: 0, 1

158

b5-19

(1DD)

PI Setpoint Value

PID Setpoint

Sets the PI target value when b5-18 = 1. Set as a percentage of

the maximum output frequency.

Default: 0.00%

Min.: 0.00
Max.: 600.00

<2>

158

b5-20

(1E2)

PI Setpoint Scaling

PID Disp Scaling

0: 0.01Hz units

1: 0.01% units

2: r/min

3: User Units

0: 0.01 Hz units

1: 0.01% units (100% = max output frequency)

2: r/min (number of motor poles must entered)

3: User-set (set scaling to b5-38 and b5-39)

Default: 1

Range: 0 to 3

158

b5-21

(1E3)

PI Sleep Input Source

PI Sleep Ref

0: PI Setpoint

1: Frequency Ref

2: Snooze Func

Input source selection for Sleep Function mode.

0: PI Setpoint

1: SFS Input

2: Snooze

Default: 1

Range: 0 to 2

159

b5-22

(1E4)

PI Snooze Level

Snooze Level

Sets the PI Snooze Function start level as a percentage of the

maximum frequency.

Default: 0%

Min.: 0

Max.: 100

159

b5-23

(1E5)

PI Snooze Delay Time

Snooze DelayTime

Sets the PI Snooze Function delay time in seconds.

Default: 0s

Min.: 0

Max.: 2600

159

b5-24

(1E6)

PI Snooze Deactivation

Level

SnoozeRestartLvl

When the PI feedback level drops below this level, the drive

returns to normal operation. Set as a percentage of the maximum

frequency.

Default: 0%

Min.: 0

Max.: 100

159

b5-25

(1E7)

PI Setpoint Boost

Setting

SetpointBoostLvl

Temporarily increases the PI setpoint to create an overshoot of

the intended PI setpoint.

Default: 0%

Min.: 0

Max.: 100

159

B.2 b: Application

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual

267

B

Parameter List