D.3 UL and CSA Standards

u

UL Standards Compliance

The UL/cUL mark applies to products in the United States and Canada. It indicates that UL has performed product testing and

evaluation, and determined that their stringent standards for product safety have been met. For a product to receive UL

certification, all components inside that product must also receive UL certification.

Figure D.3 UL/cUL Mark

This drive is tested in accordance with UL standard UL508C and complies with UL requirements. The conditions described

below must be met to maintain compliance when using this drive in combination with other equipment:

n

Installation Area

Do not install the drive to an area greater than pollution degree 2 (UL standard).

n

Ambient Temperature

IP20/NEMA Type 1 Enclosure: -10 to +40 °C
IP00 Open Type Enclosure: -10 to +50 °C

n

Main Circuit Terminal Wiring

Yaskawa recommends using closed-loop crimp terminals on all drive models. To maintain UL/cUL approval, UL Listed

closed-loop crimp terminals are specifically required when wiring the drive main circuit terminals on models 5A0041 to

5A0242. Use only the tools recommended by the terminal manufacturer for crimping.

Refer to Closed-Loop Crimp Terminal

Recommendations on page 347

for closed-loop crimp terminal recommendations.

Note:

The mark indicates the terminals for protective ground connection as defined in IEC/EN 60417-5019.

Grounding impedance: 600 V: 10 Ω or less

Wire Gauges and Tightening Torques

The wire gauges listed in the following tables are Yaskawa recommendations. Refer to local codes for proper wire gauge

selections.

Table D.2 Wire Gauge and Torque Specifications (Three-Phase 600 V Class)

Drive Model

Terminal

Recomm. Gauge

mm

2

(AWG, kcmil)

Wire Range

mm

2

(AWG, kcmil)

Screw

Size

Tightening Torque

N·m (lb.in.)

5A0003
5A0004
5A0006

R/L1, S/L2, T/L3

2.5

(14)

2.5 to 6.0

(14 to 10)

M4

1.2 to 1.5

(10.6 to 13.3)

U/T1, V/T2, W/T3

2.5

(14)

2.5 to 6.0

(14 to 10)

⊖, ⊕1, ⊕2

2.5 to 6.0

(14 to 10)

B1, B2

2.5 to 6.0

(14 to 10)

6.0

(10)

2.5 to 6.0

(14 to 10)

D.3 UL and CSA Standards

344