L6: Torque Detection

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L6-01

(4A1)

Torque Detection

Selection 1

Torq Det 1 Sel

0: Disabled

1: OL Alm at SpdAgr

2: OL Alm dur RUN

3: OL Flt at SpdAgr

4: OL Flt dur RUN

5: UL Alm at SpdAgr

6: UL Alm dur RUN

7: UL Flt at SpdAgr

8: UL Flt dur RUN

9: UL6Alm at SpdAgr

10: UL6Alm dur RUN

11: UL6Flt at SpdAgr

12: UL6Flt dur RUN

0: Disabled

1: oL3 detection only active during speed agree, operation

continues after detection

2: oL3 detection always active during run, operation continues

after detection

3: oL3 detection only active during speed agree, output shuts

down on an oL3 fault

4: oL3 detection always active during run, output shuts down

on an oL3 fault

5: UL3 detection only active during speed agree, operation

continues after detection

6: UL3 detection always active during run, operation continues

after detection

7: UL3 detection only active during speed agree, output shuts

down on an oL3 fault

8: UL3 detection always active during run, output shuts down

on an oL3 fault

9: UL6 at speed agree (alarm)

10: UL6 at run (alarm)

11: UL6 at speed agree (fault)

12: UL6 at run (fault)

Default: 0

Range: 0 to 12

133

L6-02

(4A2)

Torque Detection Level

1

Torq Det 1 Lvl

Sets the overtorque and undertorque detection level.

Default: 15%

Min.: 0

Max.: 300

134

L6-03

(4A3)

Torque Detection Time

1

Torq Det 1 Time

Sets the time an overtorque or undertorque condition must exist

to trigger torque detection 1.

Default: 10.0 s

Min.: 0.0

Max.: 10.0

134

L6-13

(62E)

Motor Underload

Protection Selection

Underload Select

0: Base Freq Enable

1: Max Freq Enable

Sets the motor underload protection (UL) based on motor

load.

0: Overtorque/undertorque detection enabled

1: Base frequency motor load enabled

Default: 0

Range: 0, 1

133

L6-14

(62F)

Motor Underload

Protection Level at

Minimum Frequency

Underload Level

Sets the UL6 detection level at minimum frequency by

percentage of drive rated current.

Default: 15%

Min.: 0

Max.: 300

133

u

L8: Drive Protection

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L8-01

(4AD)

Internal Dynamic

Braking Resistor

Protection Selection

(ERF type)

DB Resistor Prot

0: Not Provided

1: Provided

0: Resistor overheat protection disabled

1: Resistor overheat protection enabled

Default: 0

Range: 0, 1

174

L8-02

(4AE)

Overheat Alarm Level OH Pre-Alarm Lvl

An overheat alarm occurs when heatsink temperature exceeds

the L8-02 level.

Default:

<1>

Min.: 50 °C

Max.: 150 °C

174

L8-03

(4AF)

Overheat Pre-Alarm

Operation Selection

OH Pre-Alarm Sel

0: Ramp to stop

1: Coast to stop

2: Fast-Stop

3: Alarm only

4: Run@L8-19 Rate

0: Ramp to stop. A fault is triggered.

1: Coast to stop. A fault is triggered.

2: Fast Stop. Decelerate to stop using the deceleration time in

C1-09. A fault is triggered.

3: Continue operation. An alarm is triggered.

4: Continue operation at reduced speed as set in L8-19.

Default: 4

Range: 0 to 4

175

L8-05

(4B1)

Input Phase Loss

Protection Selection

Inp Ph Loss Det

0: Disabled

1: Enabled

Selects the detection of input current phase loss, power supply

voltage imbalance, or main circuit electrolytic capacitor

deterioration.

0: Disabled

1: Enabled

Default: 1

Range: 0, 1

176

L8-06

(4B2)

Input Phase Detection

Level

Inp Ph Loss Lvl

When ripple is observed in the DC bus, expansion of the input

bias is calculated. This value becomes the input phase if the

difference between the maximum and minimum values of the

ripple is greater than the value set to L8-06.
Detection Level = 100% = Voltage class x

Default:

<1>

Min.: 0.0%

Max.: 50.0%

176

B.8 L: Protection Function

294

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual