Parameter Name

Setting Range

Default

C6-02

Carrier Frequency Selection

1 to 9; A to F

Determined by A1-02 and o2-04

Settings:

C6-02

Carrier Frequency

C6-02

Carrier Frequency

C6-02

Carrier Frequency

1

2.0 kHz

5

12.5 kHz

9

Swing PWM 3

2

5.0 kHz

6

15.0 kHz

A

Swing PWM 4

3

8.0 kHz

7

Swing PWM 1

B to E

No setting possible

4

10.0 kHz

8

Swing PWM 2

F

User defined

Note:

Swing PWM uses a carrier frequency of 2.0 kHz as a base, then applies a special PWM pattern to reduce the audible noise.

Guidelines for Carrier Frequency Parameter Setup

Symptom

Remedy

Speed and torque are unstable at low speeds

Lower the carrier frequency.

Noise from the drive affects peripheral devices
Excessive leakage current from the drive
Wiring between the drive and motor is too long

<1>

Audible motor noise is too loud

Increase the carrier frequency or use Swing PWM.

<1> The carrier frequency may need to be lowered if the motor cable is too long. Refer to the following table.

Wiring Distance

Up to 50 m

Up to 100 m

Greater than 100 m

Recommended setting value for C6-02

1 to F (up to 15 kHz)

1 to 2 (up to 5 kHz),

7 (Swing PWM)

1 (up to 2 kHz), 7 (Swing PWM)

Note:

The maximum cable length is 100 m when using OLV/PM (A1-02 = 5).

n

d2-01: Frequency Reference Upper Limit

Sets the maximum frequency reference as a percentage of the maximum output frequency. This limit applies to all frequency

references.
Even if the frequency reference is set to a higher value, the drive internal frequency reference will not exceed this value.

No.

Parameter Name

Setting Range

Default

d2-01

Frequency Reference Upper Limit

0.0 to 110.0%

100.0%

n

d2-02: Frequency Reference Lower Limit

Sets the minimum frequency reference as a percentage of the maximum output frequency. This limit applies to all frequency

references.
If a lower reference than this value is entered, the drive will run at the limit set to d2-02. If the drive is started with a lower

reference than d2-02, it will accelerate up to d2-02.

No.

Parameter Name

Setting Range

Default

d2-02

Frequency Reference Lower Limit

0.0 to 110.0%

0.0%

Internal frequency

reference

d2-01

Operating

range

Frequency Reference Upper Limit

Set frequency reference

Frequency Reference Lower Limit

d2-02

Figure 4.21 Frequency Reference: Upper and Lower Limits

4.7 Basic Drive Setup Adjustments

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual

127