Setting 0: Current Detection
Setting 1: Speed Estimation

n

b3-25: Speed Search Wait Time

Sets the wait time between Speed Search restarts. Increase the wait time if problems occur with overcurrent, overvoltage, or

if the SEr fault occurs.

No.

Name

Setting Range

Default

b3-25

Speed Search Wait Time

0.0 to 300.0 s

0.5 s

n

b3-27: Start Speed Search Select

Selects a condition to activate Speed Search Selection at Start (b3-01) or External Speed Search Command 1 or 2 from the

multi-function input.

No.

Name

Setting Range

Default

b3-27

Start Speed Search Select

0, 1

0

Setting 0: Triggered when a Run Command Is Issued (Normal)
Setting 1: Triggered when an External Baseblock Is Released

n

b5-01: PI Function Setting

Enables or disables the PI operation and selects the PI operation mode.

No.

Parameter Name

Setting Range

Default

b5-01

PI Function Setting

0, 1, 3

0

Setting 0: PI Disabled
Setting 1: Output Frequency = PI Output 1

The PI controller is enabled and the PI output builds the frequency reference.

Setting 3: Output Frequency = Frequency Reference + PI Output 1

The PI controller is enabled and the PI output is added to the frequency reference.

n

b5-02: Proportional Gain Setting (P)

Sets the P gain applied to the PI input. Larger values will tend to reduce the error but may cause oscillations if set too high,

while lower values may allow too much offset between the setpoint and feedback.

No.

Name

Setting Range

Default

b5-02

Proportional Gain Setting (P)

0.00 to 25.00

2.00

n

b5-03: Integral Time Setting (I)

Sets the time constant used to calculate the integral of the PI input. The shorter the integral time set to b5-03, the faster the

offset will be eliminated. If the integral time is set too short, however, overshoot or oscillation may occur. To turn off the

integral time, set b5-03 to 0.00.

No.

Name

Setting Range

Default

b5-03

Integral Time Setting (I)

0.0 to 360.0 s

0.5 s

n

b5-04: Integral Limit Setting

Sets the maximum output possible from the integral block as a percentage of the maximum frequency (E1-04).

No.

Name

Setting Range

Default

b5-04

Integral Limit Setting

0.0 to 100.0%

100.0%

Note:

On some applications, especially those with rapidly varying loads, the output of the PI function may show a fair amount of oscillation.

Program b5-04 to apply a limit to the integral output and suppress this oscillation.

4.13 Advanced Drive Setup Adjustments

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual

155