Settings for N.C. and N.O. input for the following functions were selected

simultaneously:
• External Search Command 1 and External Search Command 2 (61 vs. 62)
• Fast Stop N.O. and Fast Stop N.C. (15 vs. 17)
• KEB for Momentary Power Loss and High Slip Braking

(65, 66, 7A, 7B vs. 68)

• Motor Switch Command and Accel/Decel Time 2 (16 vs. 1A)
• KEB Command 1 and KEB Command 2 (65, 66 vs. 7A, 7B)
• FWD Run Command (or REV) and FWD/REV Run Command (2-wire)

(40, 41 vs. 42, 43)

• External DB Command and Drive Enable (60 vs. 6A)
• Motor Switch Command and Up 2/Down 2 Command (16 vs. 75, 76)

• Check if contradictory settings have simultaneously been assigned to the

multi-function input terminals.

• Correct setting errors.

One of the following settings was entered while H1- = 2 (External

Reference 1/2):
• b1-15 = 4 (Pulse Train Input) but the pulse train input selection is not set

for the frequency reference (H6-01 > 0)

• b1-15 or b1-16 set to 3 but no option card is connected
• Although b1-15 = 1 (Analog Input) and H3-02 or H3-10 are set to 0

(Frequency Bias)

Correct the settings for the multi-function input terminal parameters.

H2- is set to 38 (Drive Enabled) and H1- is not set to 6A (Drive

Enable).

Digital Operator Display

Error Name

oPE04

Initialization Required, Term <–> Ctrl Chg

Cause

Possible Solutions

The drive, control board, or terminal board have been replaced and the

parameter settings between the control board and the terminal board no

longer match.

Set A1-03 to 5550 to load the parameter settings stored in the terminal board

to the drive. Initialize parameters after drive replacement by setting A1-03

to 1110 or 2220.

Digital Operator Display

Error Name

oPE05

Run Command/Frequency Reference Source Selection Error

Cause

Possible Solutions

Frequency reference is assigned to an option card (b1-01 = 3) and an input

option card is not connected to the drive.

Reconnect the input option card to the drive.

The Run command is assigned to an option card (b1-02 = 3) and an input

option card is not connected to the drive.

Digital Operator Display

Error Name

oPE07

Multi-Function Analog Input Selection Error
A contradictory setting is assigned to multi-function analog inputs H3-02,

H3-10, or H3-06 and PID functions conflict.

Cause

Possible Solutions

At least two analog input terminals are set to the same function (i.e., at least

two of these parameters have the same setting: H3-02, H3-10, or H3-06).

Change the settings to H3-02, H3-10, and H3-06 so that functions no longer

conflict.

Note:

Both 0 (Frequency Reference Bias) and F (Not Used) can be

set to H3-02, H3-10, or H3-06 simultaneously.

The following simultaneous contradictory settings:
• H3-02, H3-10, or H3-06 = B (PID Feedback) while H6-01

(Pulse Train Input) = 1 (PID Feedback)

• H3-02, H3-10, or H3-06 = C (PID Target Value) while H6-01 = 2

(pulse train input sets the PID target value)

• H3-02, H3-10, or H3-06 = C (PID Target Value) while b5-18 = 1

(enables b5-19 as the target PID value)

• H6-01 = 2 (PID target) while b5-18 = 1

(enables b5-19 as the target PID value)

Disable one of the PID selections.

Digital Operator Display

Error Name

oPE08

Parameter Selection Error
A function has been set that cannot be used in the motor control method

selected.

Cause

Possible Solutions

5.6 Programming Errors

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual

219

5

Troubleshooting