Setting 6: pump (secondary) application, Setting 7: pump with pi control application – Yaskawa Z1000 AC Drive HVAC User Manual

Page 120

Advertising
background image

u

Setting 5: Cooling Tower Fan with PI Control Application

Table 4.12 Cooling Tower Fan with PI Control: Parameter Settings

No.

Parameter Name

Default Setting

b1-03

Stopping Method Selection

1: Coast to Stop

b1-04

Reverse Operation Selection

0: Reverse operation enabled

b2-09

Motor Pre-Heat Current 2

10%

b5-01

PI Function Setting

1: Output frequency = PI output 1

b5-03

Integral Time Setting (I)

30 s

b5-08

PI Primary Delay Time Constant

2 s

b5-09

PI Output Level Selection

1: Reverse Output

b5-13

PI Feedback Low Detection Level

2%

b5-14

PI Feedback Low Detection Time

25 s

b5-15

PI Sleep Function Start Level

10.8 Hz

b5-16

PI Sleep Delay Time

25.5 s

C1-01

Acceleration Time 1

60 s

d2-03

Master Speed Reference Lower Limit

30%

H1-07

Multi-Function Digital Input Terminal S7 Function Selection

60: Motor Pre-Heat 1

L5-01

Number of Auto Restart Attempts

10

L6-01

Stall Prevention Selection during Deceleration

5: UL3 at speed agree (Alarm)

u

Setting 6: Pump (Secondary) Application

Table 4.13 Pump (Secondary): Parameter Settings

No.

Parameter Name

Default Setting

b1-04

Reverse Operation Selection

1: Reverse operation disabled

C1-01

Acceleration Time 1

20 s

d2-03

Master Speed Reference Lower Limit

20%

L5-01

Number of Auto Restart Attempts

10

L6-01

Stall Prevention Selection during Deceleration

5: UL3 at speed agree (Alarm)

u

Setting 7: Pump with PI Control Application

Table 4.14 Pump with PI Control: Parameter Settings

No.

Parameter Name

Default Setting

b1-04

Reverse Operation Selection

1: Reverse operation disabled

b5-01

PI Function Setting

1: Enabled (PI output becomes output frequency reference)

b5-03

Integral Time Setting (I)

15 s

b5-08

PI Primary Delay Time Constant

10.0 s

b5-13

PI Feedback Low Detection Level

2%

b5-14

PI Feedback Low Detection Time

25 s

b5-15

PI Sleep Function Start Level

72%

b5-16

PI Sleep Delay Time

25.5 s

C1-01

Acceleration Time 1

20 s

d2-03

Master Speed Reference Lower Limit

20%

L5-01

Number of Auto Restart Attempts

10

L6-01

Stall Prevention Selection during Deceleration

5: UL3 at speed agree (Alarm)

4.6 Application Selection

120

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual

Advertising