6.5 Installing Peripheral Devices

This section describes the proper steps and precautions to take when installing or connecting various peripheral devices to the

drive.

NOTICE: Use a class 2 power supply when connecting to the control terminals. Improper application of peripheral devices could result in

drive performance degradation due to improper power supply. Refer to NEC Article 725 Class 1, Class 2, and Class 3 Remote-Control,

Signaling, and Power Limited Circuits for requirements concerning class 2 power supplies.

u

Installing a Molded Case Circuit Breaker (MCCB) or Ground Fault Circuit Interrupter
(GFCI)

Install an MCCB or GFCI for line protection between the power supply and the main circuit power supply input terminals

R/L1, S/L2, and T/L3. This protects the main circuit and devices wired to the main circuit while also providing overload

protection.
Consider the following when selecting and installing an MCCB or GFCI:
• The capacity of the MCCB or GFCI should be 1.5 to 2 times the rated output current of the drive. Use an MCCB or GFCI

to keep the drive from faulting out instead of using overheat protection (150% for one minute at the rated output current).

• If several drives are connected to one MCCB or GFCI that is shared with other equipment, use a sequence that shuts the

power OFF when errors are output by using magnetic contactor (MC) as shown in

Figure 6.8

.

R/L1

MB

MCCB or GFCI

A

B

MC

MC

MC

MC

S/L2
T/L3

C

SA

A – Power supply
B – Drive

C – Control power supply

Figure 6.8 Power Supply Interrupt Wiring (Example)

WARNING! Electrical Shock Hazard. Disconnect the MCCB (or GFCI) and MC before wiring terminals. Failure to comply may result in

serious injury or death.

n

Application Precautions when Installing a GFCI

Drive outputs generate high-frequency leakage current as a result of high-speed switching. Install a GFCI on the input side of

the drive to switch off potentially harmful leakage current.
Factors in determining leakage current:
• Size of the AC drive
• AC drive carrier frequency
• Motor cable type and length
• EMI/RFI filter
If the GFCI trips spuriously, consider changing these items or use a GFCI with a higher trip level.

Note:

Choose a GFCI designed specifically for an AC drive. The operation time should be at least 0.1 s with sensitivity amperage of at least 200

mA per drive.

u

Installing a Magnetic Contactor at the Power Supply Side

Install a magnetic contactor (MC) to the drive input for the purposes explained below.

n

Disconnecting the Power Supply

Shut off the drive with an MC when a fault occurs in any external equipment such as braking resistors.

NOTICE: Do not connect electromagnetic switches or MCs to the output motor circuits without proper sequencing. Improper sequencing of

output motor circuits could result in damage to the drive.

NOTICE: Install an MC on the input side of the drive when the drive should not automatically restart after power loss. To get the full

performance life out of the electrolytic capacitors and circuit relays, refrain from switching the drive power supply off and on more than once

every 30 minutes. Frequent use can damage the drive. Use the drive to stop and start the motor.