b5-06: PI Output Limit

Sets the maximum output possible from the entire PI controller as a percentage of the maximum frequency (E1-04).

No.

Name

Setting Range

Default

b5-06

PI Output Limit

0.0 to 100.0%

100.0%

n

b5-07: PI Offset Adjustment

Sets the offset added to the PI controller output as a percentage of the maximum frequency (E1-04).

No.

Name

Setting Range

Default

b5-07

PI Offset Adjustment

-100.0 to 100.0%

0.0%

n

b5-08: PI Primary Delay Time Constant

Sets the time constant for the filter applied to the output of the PI controller. Normally, change is not required.

No.

Name

Setting Range

Default

b5-08

PI Primary Delay Time Constant

0.00 to 10.00 s

0.00 s

Note:

Useful when there is a fair amount of oscillation or when rigidity is low. Set to a value larger than the cycle of the resonant frequency.

Increasing this time constant may reduce the responsiveness of the drive.

n

b5-09: PI Output Level Selection

Reverses the sign of the PI controller output signal. Normally a positive PI input (feedback smaller than setpoint) leads to

positive PI output.

No.

Parameter Name

Setting Range

Default

b5-09

PI Output Level Selection

0, 1

0

Setting 0: Normal Output

A positive PI input causes an increase in the PI output (direct acting).

Setting 1: Reverse Output

A positive PI input causes a decrease in the PI output (reverse acting).

n

b5-10: PI Output Gain Setting

Applies a gain to the PI output and can be helpful when the PI function is used to trim the frequency reference (b5-01 = 3 or

4).

No.

Name

Setting Range

Default

b5-10

PI Output Gain Setting

0.00 to 25.00

1.00

n

b5-11: PI Output Reverse Selection

Determines whether a negative PI output reverses the direction of drive operation. This parameter has no effect when the PI

function trims the frequency reference (b5-01 = 3) and the PI output will not be limited (same as b5-11 = 1).

No.

Parameter Name

Setting Range

Default

b5-11

PI Output Reverse Selection

0, 1

0

Setting 0: Reverse Disabled

Negative PI output will be limited to 0 and the drive output will be stopped.

Setting 1: Reverse Enabled

Negative PI output will cause the drive to run in the opposite direction.

n

b5-12: PI Feedback Loss Detection Selection

Enables or disables the feedback loss detection and sets the operation when a feedback loss is detected.

4.13 Advanced Drive Setup Adjustments

156