Yaskawa Z1000 AC Drive HVAC User Manual

Page 304

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

S3-05

(321E) Secondary PI Setpoint

Value

PI2 Setpoint

Sets the secondary PI controller target value

Default: 0.00

<1>

Min.: 0.00
Max.: 600.00

<2>

S3-06

(321F)

Secondary PI

Proportional Gain

Setting

PI2 Gain

Sets the proportional gain of the secondary PI controller. A setting

of 0.00 disables P control.

Default: 1.00

Min.: 0.00

Max.: 25.00

S3-07

(3220)

Secondary PI Integral

Time Setting

PI2 I Time

Sets the integral time for the secondary PI controller. A setting of

0.0s disables integral control.

Default: 1.0 s

Min.: 0.0

Max.: 360.0

S3-08

(3221)

Secondary PI Integral

Limit Setting

PI2 I Limit

Sets the maximum output possible from the integrator.

Default:

100.0%

Min.: 0.0

Max.: 100.0

S3-09

(3222)

Secondary PI Output

Upper Limit

PI2 Upper Limit

Sets the maximum output possible from the secondary PI

controller.

Default:

100.0%

Min.: 0.0

Max.: 100.0

S3-10

(3223)

Secondary PI Output

Lower Limit

PI2 Lower Lim

Sets the minimum output possible from the secondary PI

controller.

Default: 0.00%

Min.: -100.00

Max.: 100.00

S3-11

(3224)

Secondary PI Output

Level Selection

PI2 Out Lvl Sel

0: Normal Character

1: Rev Character

0: Normal Output (direct acting)

1: Reverse Output (reverse acting)

Default: 0

Range: 0, 1

S3-12

(3225)

Secondary PI Disable

Mode

PI2 Disable Mode

0: No output

1: Lower Limit

(S3-10)

2: Setpoint

0: No output (0%)

1: Lower Limit (S3-10)

2: Setpoint

Default: 0

Range: 0 to 2

S3-13

(3226)

Secondary PI Low

Feedback Detection

Level

PI2 Low FB Lvl

Sets the secondary PI low feedback detection level.

Default: 0.00

<1>

Min.: 0.00
Max.: 600.00

<2>

S3-14

(3227)

Secondary PI Low

Feedback Detection

Time

PI2 Low FB Time

Sets the secondary PI low feedback detection delay time in

seconds.

Default: 1.0 s

Min.: 0.0

Max.: 25.5

S3-15

(3228)

Secondary PI High

Feedback Level

PI2 High FB Lvl

Sets the secondary PI high feedback detection level.

Default: 100.00

<1>

Min.: 0.00
Max.: 600.00

<2>

S3-16

(3229)

Secondary PI High

Feedback Detection

Time

PI2 High FB Tim

Sets the secondary PI high feedback detection delay time in

seconds.

Default: 1.0 s

Min.: 0.0

Max.: 25.5

S3-17

(322A) Secondary PI Feedback

Detection Selection

PI2 FB Det Sel

0: PI2 Enabled

1: Always

0: Secondary PI enabled

1: Always

Default: 0

Range: 0, 1

<1> Unit is determined by S3-04.
<2> Upper limit is S3-02, decimal placeholder is determined by S3-03.

B.11 S: Special Application

304

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual